Add a PowerFlex 525 Drive to a Controller Project Chapter 2
3.
Change the parameters listed in the following table to values shown.
4.
Close the Parameter List dialog box.
The parameters are saved in the drive.
Parameter
Name
Value
Parameter 40
Autotune
Ready/Idle
Parameter 47
Speed Reference1
EtherNet/IP
Parameter 62
DigIn TermBlk 02
Not Used
Parameter 63
DigIn TermBlk 03
Not Used
Parameter 64
2-Wire Mode
Edge Trigger
Parameter 65
DigIn TermBlk 05
Not Used
Parameter 66
DigIn TermBlk 06
Not Used
Parameter 67
DigIn TermBlk 07
Not Used
Parameter 68
DigIn TermBlk 08
Not Used
Parameter 153
EN Data In 1
0
Parameter 154
EN Data In 2
0
Parameter 155
EN Data In 3
0
Parameter 156
EN Data In 4
0
Parameter 157
EN Data Out 1
0
Parameter 158
EN Data Out 2
0
Parameter 159
EN Data Out 3
0
Parameter 160
EN Data Out 4
0