3 model numbers, 4 drive description – Rockwell Automation FlexPak 3000 DC Drive Version 4.3 User Manual

Page 10

Advertising
background image

1-2

FlexPak 3000 DC Drive Hardware Reference Version 4.3

1.3

Model Numbers

Drive specific data, such as horsepower (or output current), regenerative or non-
regenerative type, line voltage, chassis or enclosure type, software version and UL
certification, can be determined by the drive model number. The model number
structure is shown in figure 1.2.

Up to 300 HP, drives configured for 460 VAC input can be converted to 230 VAC input
at one half the 460 VAC horsepower rating by installing a 460 to 230 Volt Conversion
Kit (M/N 916FK0100, 1-60 HP, or M/N 916FK0200, 75-150 HP). Instruction manual
D2-3329, which is supplied with the kit, provides installation instructions. For drives
above 300 HP, contact your local Reliance Electric sales office for assistance.

1.4

Drive Description

The drive is a full-wave power converter without back rectifier, complete with a digital
current minor loop and a digital major loop for armature voltage or speed regulation by
tachometer feedback. Figure 1.3 shows a block diagram of the drive.

Figure 1.2 – Model Number Structure

150FR4042

F = FlexPak 3000 product line

Software version number 0-9, A-Z

B = Regenerative drives with inverting fault breaker

K = Kits

R = Regenerative drives

N = Non-regenerative drives

0 = Chassis
7 = Integrator

0 = No listing
1 = U/L and C-U/L
2 = U/L, C-U/L, and CE

For horsepower-rated drives:

Horsepower under 1000

For current-rated drives:

Rated output armature current

2 = 230 volts
3 = 380/415 volts
4 = 460 volts
7 = Integrator
8 = European Power Module

Advertising