Rockwell Automation FlexPak 3000 DC Drive Version 4.3 User Manual
Page 76

B-4
FlexPak 3000 DC Drive Hardware Reference Version 4.3
B.2.4 Selecting an Operator Control Station
If an operator control station is connected to the drive, its enclosure must be
conductive metal. The enclosure cover must be bonded to an internal ground point
with a braided strap across the hinge. Standard industrial operator devices, such as
pushbuttons, switches, and meters, can be used.
Table B.2 – AC Mains Filter Model Numbers for 3 to 300 HP @ 460 VAC FlexPak 3000 Drives
HP
Rating
AC Full
Load
Amps
Minimum
Inductance
(in microhenries
(
µ
H))
AC Mains Filter
Model Number
AC Mains
Inductor
3
10
1680
3DF4353
608895-63H
5
12
1400
3DF4353
608895-63H
7.5
15
1125
3DF4353
608895-63K
10
18
1000
3DF4354
608895-63K
15
24
700
3DF4354
608895-63M
20
31
550
3DF4355
608895-63P
25
39
430
3DF4355
608895-63P
30
45
375
3DF4355
608895-63R
40
60
270
3DF4357
608895-63W
50
74
225
3DF4357
608895-63W
60
86
195
3DF4357
608895-63Y
75
110
150
3DF4359
608895-63AA
100
143
120
3DF4359
608895-63AC
125
177
95
3DF4359
608895-63AE
150
213
80
3DF4359
608895-63AG
200
281
60
3DF4359
608895-63AK
250
351
48
Two 3DF4359
filters connected
in parallel
608895-63AN
300
421
40
608895-63AR