B-4

FlexPak 3000 DC Drive Hardware Reference Version 4.3

B.2.4 Selecting an Operator Control Station

If an operator control station is connected to the drive, its enclosure must be
conductive metal. The enclosure cover must be bonded to an internal ground point
with a braided strap across the hinge. Standard industrial operator devices, such as
pushbuttons, switches, and meters, can be used.

Table B.2 – AC Mains Filter Model Numbers for 3 to 300 HP @ 460 VAC FlexPak 3000 Drives

HP

Rating

AC Full

Load

Amps

Minimum

Inductance

(in microhenries

(

µ

H))

AC Mains Filter

Model Number

AC Mains

Inductor

3

10

1680

3DF4353

608895-63H

5

12

1400

3DF4353

608895-63H

7.5

15

1125

3DF4353

608895-63K

10

18

1000

3DF4354

608895-63K

15

24

700

3DF4354

608895-63M

20

31

550

3DF4355

608895-63P

25

39

430

3DF4355

608895-63P

30

45

375

3DF4355

608895-63R

40

60

270

3DF4357

608895-63W

50

74

225

3DF4357

608895-63W

60

86

195

3DF4357

608895-63Y

75

110

150

3DF4359

608895-63AA

100

143

120

3DF4359

608895-63AC

125

177

95

3DF4359

608895-63AE

150

213

80

3DF4359

608895-63AG

200

281

60

3DF4359

608895-63AK

250

351

48

Two 3DF4359

filters connected

in parallel

608895-63AN

300

421

40

608895-63AR