FlexPak 3000 DC Drive Hardware Reference Version 4.3

Step 4. Connect a suitable equipment grounding conductor to the motor frame, the

transformer enclosure if used, and the drive enclosure. Run this conductor
unbroken to the grounding electrode.

Step 5. Connect the GND (green/ground) wire brought in with the incoming AC

power line to the drive ground point.

Step 6. Tighten chassis ground connections per table 2.1.

Table 2.1 – Chassis Ground Torgue Requirements

Hardware Size

Tightening Torque

M5

18 lb/in (2 Nm)

M6

33 lb/in (3.7 Nm)

M8

100 lb/in (11.3 Nm)

M10

200 lb/in (23 Nm)

Lug with 14-10 AWG

35 lb/in (4 Nm)

Lug with 8 AWG

40 lb/in (4.5 Nm)

Lug with 6-4 AWG

45 lb/in (5.1 Nm)