Drive Setup and Adjustment

3-5

3.4.1 Set the Regulator Type (Jumper J15)

J15 determines whether the drive uses speed/voltage or torque/current regulation.

When

CURRENT

is selected, only the terminal strip, the DeviceNet Communication

Board, or the AutoMax Network Communication Board can be used as a control
source. When J15 is set to

CURRENT

, the drive is fixed in auto mode and cannot be

changed.

Also note that speed/voltage parameters must be set to provide overspeed protection
for the drive.

Table 3.1 – Jumper Settings

JUMPER

DEFAULT

SETTING

FINAL SETTING

J15 (REGULATOR TYPE)

SPEED

J16 (OIM PROGRAM)

ENABLE

J20 (FIELD LOSS DETECT)

ENABLE

J21 (FIELD SUPPLY JUMPER)

B-C

J19 (MANUAL REF)

POT

J14 (TACH V RANGE)

62

J11 (TACH V SCALE)

16

J10 (AUTO REF)

VOLTS

J12 (AUTO REF)

VOLTS

J18 (ARM I FB RB)

Position 4

J26

(not used)

Jxx is not used. Do not
install a shorting bar
across pins of this jumper.

J27 (SPARE 1)

(not used)

J28 (FILTER SELECT)

(not used)

J29 (SPARE 2)

(not used)

J30 (POWER UNIT)

LOW