Install and Wire the Drive

2-19

Important: The tightening torque in the table applies to the wiring device (stud or

terminal board) provided. When an input or an output device (breaker or
lug kit) is added, refer to the kit instructions for tightening specifications.

Table 2.3 – AC Line Torque Recommendations

AC Input

Horsepower

230 VAC

460 VAC

1.5

55 lb-in (6.2 Nm)

----------

2

55 lb-in (6.2 Nm)

----------

3

55 lb-in (6.2 Nm)

55 lb-in (6.2 Nm)

5

55 lb-in (6.2 Nm)

55 lb-in (6.2 Nm)

7.5

55 lb-in (6.2 Nm)

55 lb-in (6.2 Nm)

10

55 lb-in (6.2 Nm)

55 lb-in (6.2 Nm)

15

120 lb-in (13.6 Nm)

55 lb-in (6.2 Nm)

20

120 lb-in (13.6 Nm)

55 lb-in (6.2 Nm)

25

120 lb-in (13.6 Nm)

55 lb-in (6.2 Nm)

30

120 lb-in (13.6 Nm)

120 lb-in (13.6 Nm)

40

200 lb-in (22 Nm)

120 lb-in (13.6 Nm)

50

200 lb-in (22 Nm)

120 lb-in (13.6 Nm)

60

200 lb-in (22 Nm)

120 lb-in (13.6 Nm)

75

200 lb-in (22 Nm)

200 lb-in (22 Nm)

100

200 lb-in (22 Nm)

200 lb-in (22 Nm)

125

350 lb-in (40 Nm)

200 lb-in (22 Nm)

150

350 lb-in (40 Nm)

200 lb-in (22 Nm)

200

----------

200 lb-in (22 Nm)

250

----------

350 lb-in (40 Nm)

300

----------

350 lb-in (40 Nm)

400

----------

350 lb-in (40 Nm)

500

----------

350 lb-in (40 Nm)

600

----------

350 lb-in (40 Nm)

Rated Output Amps

AC Input

7A

55 lb-in (6.2 Nm)

29A

55 lb-in (6.2 Nm)

55A

120 lb-in (13.6 Nm)

110A

120 lb-in (13.6 Nm)

265A

200 lb-in (22 Nm)