Rockwell Automation FlexPak 3000 DC Drive Version 4.3 User Manual
Page 69

Technical Specifications
A-3
Table A.6 – Power Ratings
1
(230/460 VAC)
1
When applying FlexPak 3000 drives to a power distribution system with KVA capacity in excess of 5 times the smallest drive rating, the
use of an isolation transformer or line reactors of similar impedance is required. Note also that the drives are designed for a maximum of
three units per transformer.
HP
Full Load Rated
RMS AC Line
Current
(Amperes)
Full Load Rated
DC Armature
Current
(Amperes)
Rated Field
Current
(Amperes)
Maximum
Symmetrical AC
Fault Current
(Amperes)
Min.
Source
KVA
230 VAC
460 VAC
240 VDC
500 VDC
150 VDC
300 VDC
230 VAC
460 VAC
1.5
10
—
7
—
10
—
5000
—
4
2
11
—
9
—
10
—
5000
—
5
3
13
10
12
6
10
10
5000
5000
6
5
19
12
20
10
10
10
5000
5000
7.5
7.5
26
15
29
14
10
10
5000
5000
11
10
33
18
38
19
10
10
5000
5000
15
15
48
24
55
27
10
10
5000
5000
20
20
63
31
73
35
15
10
10000
5000
27
25
80
39
93
45
15
10
10000
5000
34
30
94
45
110
52
15
10
10000
5000
40
40
125
63
146
73
15
15
25000
10000
51
50
154
74
180
86
15
15
25000
10000
63
60
186
86
218
100
15
15
25000
10000
75
75
226
110
265
129
15
15
25000
25000
93
100
307
143
360
167
15
15
30000
25000
118
125
370
177
434
207
15
15
30000
25000
145
150
443
213
521
250
15
15
30000
25000
175
200
—
281
—
330
—
15
—
30000
220
250
—
351
—
412
—
15
—
30000
275
300
—
421
—
495
—
15
—
30000
330
400
—
567
—
667
—
15
—
75000
440
500
—
680
—
800
—
15
—
75000
550
600
—
816
—
960
—
15
—
75000
660