Rockwell Automation FlexPak 3000 DC Drive Version 4.3 User Manual

Page 69

Advertising
background image

Technical Specifications

A-3

Table A.6 – Power Ratings

1

(230/460 VAC)

1

When applying FlexPak 3000 drives to a power distribution system with KVA capacity in excess of 5 times the smallest drive rating, the
use of an isolation transformer or line reactors of similar impedance is required. Note also that the drives are designed for a maximum of
three units per transformer.

HP

Full Load Rated

RMS AC Line

Current

(Amperes)

Full Load Rated

DC Armature

Current

(Amperes)

Rated Field

Current

(Amperes)

Maximum

Symmetrical AC

Fault Current

(Amperes)

Min.

Source

KVA

230 VAC

460 VAC

240 VDC

500 VDC

150 VDC

300 VDC

230 VAC

460 VAC

1.5

10

7

10

5000

4

2

11

9

10

5000

5

3

13

10

12

6

10

10

5000

5000

6

5

19

12

20

10

10

10

5000

5000

7.5

7.5

26

15

29

14

10

10

5000

5000

11

10

33

18

38

19

10

10

5000

5000

15

15

48

24

55

27

10

10

5000

5000

20

20

63

31

73

35

15

10

10000

5000

27

25

80

39

93

45

15

10

10000

5000

34

30

94

45

110

52

15

10

10000

5000

40

40

125

63

146

73

15

15

25000

10000

51

50

154

74

180

86

15

15

25000

10000

63

60

186

86

218

100

15

15

25000

10000

75

75

226

110

265

129

15

15

25000

25000

93

100

307

143

360

167

15

15

30000

25000

118

125

370

177

434

207

15

15

30000

25000

145

150

443

213

521

250

15

15

30000

25000

175

200

281

330

15

30000

220

250

351

412

15

30000

275

300

421

495

15

30000

330

400

567

667

15

75000

440

500

680

800

15

75000

550

600

816

960

15

75000

660

Advertising