2-18

FlexPak 3000 DC Drive Hardware Reference Version 4.3

2.5.3 Wire AC Power to the Drive

Step 1. Size the AC line supply conductors for the specific drive rating and according

to all applicable codes.

Step 2. Connect the AC line supply to the termination points located at the right top

of the drive or to the disconnect. See figures 2.14 through 2.17.

Step 3. (Integrator drives only) Connect the line fuses (1FU, 2FU, 3FU), field fuses

(6FU, 7FU, 8FU), and the FN contactor to the drive as shown in figure 2.18.
Note that the line and field fuses must be wired as shown in figure 2.18 to
ensure proper phase relationships.

Step 4. (Integrator drives only) Connect the AC line supply to the line fuses (1FU,

2FU, 3FU).

Step 5. Tighten incoming AC line connections per table 2.3.

!

ATTENTION:The user is responsible for conforming to the National
Electric Code (NEC/CEC) and all other applicable local codes. Wiring
practices, grounding, disconnects, and overcurrent protection are of
particular importance. Size and install wiring in conformance with the
NEC/CEC and all other applicable codes. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION:The drive requires a three-phase power source of either
230, 380, 415, or 460 VAC, 50 or 60 Hz. If the correct voltage is not
available, a transformer must be installed between the power source and
the drive. Do not connect the drive to a power source with available
symmetrical short circuit capacity in excess of the power source capacity
listed in Appendix A, tables A.6 and A.7. Failure to observe these
precautions could result in bodily injury or equipment damage.