3: Install and Wire The Drive

DANGER

ONLY QUALIFIED ELECTRIĆ

CAL PERSONNEL FAMILIAR

WITH THE CONSTRUCTION

AND OPERATION OF THIS

EQUIPMENT AND THE HAZĆ

ARDS INVOLVED SHOULD

INSTALL, ADJUST, OPERATE

AND/OR

SERVICE

THIS

EQUIPMENT.

READ AND

UNDERSTAND THIS MANUAL

IN ITS ENTIRETY BEFORE

PROCEEDING. FAILURE TO

OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

DANGER

THE USER IS RESPONSIBLE

FOR CONFORMING TO THE

NATIONAL

ELECTRICAL

CODE (NEC) AND ALL OTHER

APPLICABLE LOCAL CODES

WITH RESPECT TO WIRING

PRACTICES,

GROUNDING,

DISCONNECTS, AND OVERĆ

CURRENT PROTECTION ARE

OF

PARTICULAR

IMPORĆ

TANCE.

FAILURE TO OBĆ

SERVE THIS PRECAUTION

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

DANGER

THIS EQUIPMENT IS AT LINE

VOLTAGE WHEN AĆC POWER

IS CONNECTED. DISCONĆ

NECT AND LOCKOUT ALL

UNGROUNDED

CONDUCĆ

TORS OF THE AĆC POWER

LINE. FAILURE TO OBSERVE

THIS PRECAUTION COULD

RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

General

This Section outlines the

procedures that are to be followed

to properly install the FlexPak Plus

SingleĆPhase DĆC Drive. Refer to

Figure 3Ć2 for mounting dimensions.

Install the Controller -

Panel Layout

The controller is designed as a

panel mount unit and must be hung

within 10_ of vertical with the rear of

the chassis firmly bolted to the

mounting surface. Do not mount the

chassis in a horizontal position.
Leave 2 inches (50 mm) clearance

between the top of one Drive and

the bottom of another Drive. This

area must remain unobstructed for

proper air circulation through the

heat sink. Do not place the

controller directly in a corner, leave

at least 8 inches (200 mm) from the

top and 6 inches (150 mm) from the

bottom of the cabinet.
Regardless of the above placement

guidelines, the user is responsible

for ensuring that the Controller's

ambient specification of 0 to 55_C i s

met. Relative humidity must be kept

within 5% to 95% without

condensation.

8 i n.

(200 mm

)

2 i n.

(50 mm

)

6 i n.

(150 mm

)

Figure 3.1 - Enclosure Mounting

Minimum Distances