Drive setćup procedure – Rockwell Automation FlexPak Plus DC Drive User Manual

Page 26

Advertising
background image

4:4

Table 4Ć2. Control Power Voltages.

Function

Terminal(s)

/Pin(s)

Nominal Values

(VDC)

Unregulated +20 VDC

256

+20 VDC +5%

Unregulated Ć20 VDC

271

Ć20 VDC +5%

Regulated +11.2 VDC

56

+11.2 VDC +5%

Regulated Ć11.2 VDC

71

Ć11.2 VDC +5%

Drive SetĆUp Procedure

Basic Regulator Maximum

Safe Operating Adjustments

The following adjustments are

available on the Basic Regulator

(see Figure 4Ć3):

CAUTION: The following adjustĆ

ments are maximum safe operĆ

ating ranges. Potentiometers on

the regulator, particularly curĆ

rent limit, may exceed these

ranges. Failure to observe this

precaution could result in damĆ

age to, or destruction of, equipĆ

ment.

0

J8

COM

TEST

0

0

0

0

C T A

56

17
16

271
256
126

57

71

419

85

87
86

319
219

56

57

2.5

3.7

FDBK.

CLIP FOR

50HZ

J7

45

55

60

65

70

0

MAX. SPD.

MIN. SPD.

ACCEL. SPD.

DECEL. SPD.

I LIMIT

IR COMP

Maximum Speeed

ā 50 to 100% of motor base speed

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Minimum Speed

0 to 100% of motor base speed

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Current Limit

10 to 150% of armature voltage at rated load

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IR Drop Compensation

0 to 2% of rated load

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Acceleration Rate

āā0.5to 30 seconds

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Deceleration Rate

āā0.5to 30 seconds

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 4Ć3. Regulator Function Potentiometers