Rockwell Automation FlexPak Plus DC Drive User Manual

Page 45

Advertising
background image

5:15

Yes

Replace TACH feedback

kit, reconnect feedback

selection jumper to the T"

position for TACH feedĆ

back and restart drive.

If using TACH feedback,

change feedback selection

jumper to the A" position for

armature voltage feedback

and restart the drive.

Does motor

still runaway?

Remove TACH leads from

the TACH feedback kit.

Measure voltage of TACH.

CompareTACH voltageto

RPM speed of motor being

driven.

Is proper

TACH

present?

Verify that proper selection

of jumpers on the TACH

feedback kit has been seĆ

lected for type of TACH beĆ

ing used.

Arejumpers

selected

correctly?

Correct the problem.

Fixed?

Done

Start

Note: #1: Contact local sales/service office.

No

Replace TACH and reconĆ

nect feedback jumper to

theT" posiiton for TACH

feeback and restart the

drive.

Fixed?

Done

Yes

No

Fixed?

Done

Yes

Yes

No

See Note #1

No

Yes

Check thevoltageat terĆ

minals F1 and F2 on 2TB

of thefield supply kit (if

applicable)

Yes

Remove motor field leads

from terminals F1 and F2,

makea continuity check

between motor field leads.

Is proper

field voltage

present for

motor being

used?

Yes

No

Is

continuity

present?

Replace

Regulator

Board

Correct the

problem

Fixed?

Done

Yes

No

SeeNote#1

Replace field

supply

Fixed?

Done

Yes

No

Yes

No

No

Yes

No

Is drive a speed or voltĆ

ageregulator?

Speed Reg.

Replace

Regulator

Board

Fixed?

Done

No

SeeNote#1

DANGER

THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE EXTREME

CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT

IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Figure 5Ć9. Motor Runs Away.