Rockwell Automation FlexPak Plus DC Drive User Manual
Page 43
Advertising
![background image](/manuals/581666/43/background.png)
5:13
Has jumper
been cut or
removed?
Replace Regulator Board
Fixed?
See Note #1
Done
C
Yes
No
Done
Fixed?
Yes
No
See Note #1
No
Yes
Correct the
problem
*
Note #1: Contact local sales/service office.
*Install a jumper between terminal 26 and 126.
From
previous
page
DANGER
SOME OF THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE
EXTREME CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION
COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
Figure 5Ć8. M" Contactor PicksĆUp But Motor Does Not Run. (Continued)