5:8

Bad Aux contact on contacĆ

tor. Replace FM contactor or

Aux (if possible).

Apply AĆC Power and check for proper

line voltage between terminals 51

and 52.

Do you have

correct

voltage

?

Start

Yes

No

3C

No

Check for open

fuses/disconnect

Fixed

?

Done

Yes

No

Yes

Note #1: Contact local sales/service office.

Do you

have an open

circuit

?

Replace or repair fuses/

disconnect problem

Problem is with AĆC line

voltage supply. Correct

this problem.

Fixed

?

Done

Yes

No

Does FM

contactor pickup

when start button

is pressed

?

While pressing start button check for

24VDC between pins 36 and 139

Voltage

Present

?

Check for continuity between pin 38

and 39 on the regulator card.

Continuity

OK

?

Open foil on regulator board.

Replace board.

Bad CR relay. Replace

regulator board.

No

Fixed

?

Done

Yes

No

See Note #1

Yes

Yes

No

No

No

Go to 3B

Yes

DANGER

SOME OF THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE

EXTREME CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE BODILYINJURYOR LOSS OF LIFE.

Figure 5Ć6. Drive Doesn't Start.