Rockwell Automation FlexPak Plus DC Drive User Manual

Page 39

Advertising
background image

5:9

Replace

Control

Transformer

Check for 24VAC between

pins 481 and 482 of the

regulator board.

3B

Remove power from drive and check

for cotinuity between terminals 32

and 132.

Is there

continuity?

Check for 24VDC between terminal 132

and PIN 139 (COM).

Is

Voltage

Present?

While pressing start button, check for

24VDC between terminal 38 and Pin

139 (COM).

Is

Voltage

Present?

Check to see if Jumper J9 on the reguĆ

lator board has been cut or removed.

Has

jumper

been cut or

removed?

With AĆC power removed, check contiĆ

nuity between Pins 39 and 139.

Is there

continuity?

Replace regulator board.

Fixed?

Done

No

Yes

No

No

3C

Yes

Check for a motor therĆ

mostat or a jumper wired

to terminals 32 and132.

Is there a

thermostat/jumper

wired there?

Thermostat or jumper

is malfunctioning, corĆ

rect the problem.

Yes

No

Wire the motor thermoĆ

stat to terminals 32 and

132. If motor has no therĆ

mostat, install a jumper.

Fixed?

No

Yes

Done

No

Is

voltage

present?

Fixed?

Done

Yes

No

Yes

No

Replace regĆ

ulator board

Fixed?

No

Yes

Done

Yes

There is a problem with

the start/stop circuitry.

No

Yes

Correct the

problem.

Fixed?

Yes

Done

No

Correct the

problem.

Fixed?

Yes

Done

No

Coil of FM contactor is

open. Replace FM conĆ

tactor.

No

Fixed?

Yes

Done

No

Yes

Yes

Yes

Done

Fixed?

Note: #1: Contact local sales/service office.

DANGER

THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE EXTREME

CAUTION AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION COULD

RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Figure 5Ć6. Motor Doesn't Start. (Continued)