Install A Disconnect

DANGER

THIS EQUIPMENT IS AT LINE

VOLTAGE WHEN AĆC POWER

IS CONNECTED. DISCONĆ

NECT AND LOCKOUT ALL

UNGROUNDED

CONDUCĆ

TORS OF THE AĆC POWER

LINE. FAILURE TO OBSERVE

THESE

PRECAUTIONS

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

1. Any fused disconnect or circuit

breaker in the incoming AĆC line

must accommodate a maximum

symmetrical AĆC fault current of

5,000 amperes.

The National Electrical Code

requires that a two pole, fused

disconnect switch be installed on

the incoming AĆC line ahead of the

Drive. Fuses for this disconnect

switch should be chosen from

Table 2Ć3. They should be dual

element, slow blow type, or

Class K5.

The disconnect switch should be

within clear view of machine

operating and maintenance

personnel for easy access and

safety. An openĆtype switch with

provisions for a padlock is

recommended.

Wire The Drive

Reference Figure 3Ć3 when wiring

the drive.