Install a disconnect, Wire the drive – Rockwell Automation FlexPak Plus DC Drive User Manual
Page 13

3:3
Install A Disconnect
DANGER
THIS EQUIPMENT IS AT LINE
VOLTAGE WHEN AĆC POWER
IS CONNECTED. DISCONĆ
NECT AND LOCKOUT ALL
UNGROUNDED
CONDUCĆ
TORS OF THE AĆC POWER
LINE. FAILURE TO OBSERVE
THESE
PRECAUTIONS
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
1. Any fused disconnect or circuit
breaker in the incoming AĆC line
must accommodate a maximum
symmetrical AĆC fault current of
5,000 amperes.
The National Electrical Code
requires that a two pole, fused
disconnect switch be installed on
the incoming AĆC line ahead of the
Drive. Fuses for this disconnect
switch should be chosen from
Table 2Ć3. They should be dual
element, slow blow type, or
Class K5.
The disconnect switch should be
within clear view of machine
operating and maintenance
personnel for easy access and
safety. An openĆtype switch with
provisions for a padlock is
recommended.
Wire The Drive
Reference Figure 3Ć3 when wiring
the drive.