Rockwell Automation FlexPak Plus DC Drive User Manual
Page 14

3:4
REMOTE OPERATOR
INTERFACE
NOTES:
These signals must be run in a
separate magnetic conduit to
minimize the possibility of noise
pickup. Use either twisted double
or twisted triple conductor wire,
2 twists per inch, stranded copper,
AWG #16,600 VAC rated, polyvinyl
chloride insulation, with a temperaĆ
ture range of 40-105_C (104-221_F)
When the Auto/Manual Switch is
used, wire 426 is connected to the
Auto/Manual Switch rather than
the Speed Pot.
Motor nameplate field voltage must
match controller nameplate field
voltage.
Use convenience terminals for
#14 AWG maximum wire size.
T/C Reference series field
connection S
1
/S
2
.
If motor is a permanent magnet
design, do not wire F
1
or F
2.
* Blank Terminals
3
3
ă57
ă71
199
ă28
426
ă20
326
126
ă26
ă65
ă66
ă39
ă67
ă35
ă38
ă32
426
326
3 2 1
3 2 1
1
1
2
20
426
28
57
199
71
2
TYPICAL REMOTE OPERATOR CONTROLS
(Rear View)
SPEED Pot
TORQUE Pot
AUTO
MANUAL
AUTO/MANUAL
Switch
JOG/RUN
Switch
35
32
38
65
67
66
39
FWD/REV
Switch
START/STOP
Switch
REV
FWD
*
*
+ -
+ -
L1 L2 A1 A2
51 52 47 45
32 132 F1 F2
TACHOMETER
1
T1 (+)
T2 (-)
P1 P2 F1 F2 A1 A2
(32) (132)
DĆC Drive Motor
Single Phase
AĆC Power
4
TACHOMETER
FEEDBACK KIT
1
2
4
6
5
INSTRUMENT
INTERFACE
or
VOLTAGE FOLĆ
LOWER
KIT
PROCESS CONTROL
AUTO REFERENCE
INPUTS
1
6
5
Figure 3Ć3. Drive Connection Diagram.