Rockwell Automation FlexPak Plus DC Drive User Manual

Page 9

Advertising
background image

2:4

Table 2Ć2. Isolation Transformer Specifications.

HP

kVA

Primary Vac

Secondary

Vac

Reliance Part

Number

1/4

0.5

230/460

115

77530Ć16A

0.5

575

115

77530Ć17A

1/3

0.75

230/460

115

77530Ć16B

0.75

575

115

77530Ć17B

1/2Ć3/4

1.5

115

115

77530Ć15D

230/460

115

77530Ć16D

575

115

77530Ć17D

230/460

230

77530Ć16D

575

230

77530Ć17D

1

2.0

230/460

230

77530Ć16E

575

230

77530Ć17E

1Ć1 1/2

3.0

230/460

230

77530Ć16F

575

230

77530Ć17F

2

5.0

230/460

230

77530Ć16G

575

230

77530Ć17G

3Ć5

10.0

230/460

230

77530Ć16H

575

230

77530Ć17H

NOTE: Smaller drives through 3/4 HP @ 115 VAC and 2.0 HP @ 230 VAC may be used with permanent magnetic field motors, and those drive

models are supplied without a DĆC field supply.

Table 2Ć3. Fuse Requirements.

Dual Element Class

K5, RK5, 250VAC Fuse

HP

AĆC Line

Volts

Quantity

AMP

Reliance Part

Number

1/4Ć3/4

115

1

1

15

64676Ć1W

1/2Ć1 1/2

230

2

15

64676Ć1W

2Ć3

230

2

30

64676Ć1Z

5

230

2

50

64676Ć1AD

1

Install fuse in input line L1 (hot line).

Table 2Ć4. Controller Modification Kits.

Kit Model

Number

Kit Name

Functional Description

Instruction

Manual

14C214

Dynamic Braking Resistor

1/4 to 1/2 HP @115 VAC

2.0 to 3.0 HP @230 VAC

Dynamic braking resistor for reduced stopping time.

-

14C215

3/4 HP @115 VAC

-

14C216

1/2 to 1 1/2 HP @230 VAC

5 HP @230 VAC

-

14C219

(B/M 54379Ć1)

Auxiliary M" Contactor

Provides isolated Form C contact status of Drive M"

Contactor.

-

14C221

Tachometer Feedback

Interfaces between the tachometer and the regulator

when speed regulations is desired.

DĆ3969

14C222

Instrument Interface/Preset

Speed Reference

Allows drive to follow an instrument signal of 0Ć5, 1Ć5,

4Ć20 or 10Ć50 miiliamp signal. Can also be used for

drive preset speed reference.

DĆ3967

Advertising