Wire the dćc motor to the controller, Install the field supply, Wire the field supply – Rockwell Automation FlexPak Plus DC Drive User Manual

Page 19

Advertising
background image

3:9

NOTE: When Reversing is used, the J9 Jumper on the Regulator Board must be cut.

1

1

Control transformer secondary winding

481

482

approx. 24 VDC

MOTOR

OVERLOAD

132

32

STOP

START

38

RUN

JOG

35

CR

38

RM

FM

36

36

CR

10

m

fd

STATIC

LOGIC

139

RM

220 MFD

FM & RM Contactor may not be supplied by Reliance

- Pin Connection

- Wire Terminal Board

FM

65

65

REVERSE

67

38

139

220 MFD

RM

66

66

FORWARD

39

FM

39

1

Figure 3Ć6. Reversing Drive Control Circuit.

Wire the DĆC Motor to the

Controller

1. Size the motor armature circuit

conductors for the specific

controller rating and according

to applicable codes.

2. Run the DĆC motor armature

leads and the shunt field supply

leads (if a permanent magnet

field motor is not used). See

Figure 3Ć3A for the Motor

Armature Circuit Connection.

Refer to Wire the Field Supply"

in this manual for field supply

connections.

Install the Field Supply

The Field Supply Kit provides

fullĆwave field excitation for

shuntĆwound DĆC motors. It may be

optionally applied to controllers

from 1/4 thru 1 1/2 HP. (It is a

standard feature for 3 and 5 HP

FlexPak Plus controllers.)
The Kit is an assembly consisting of

a terminal block (F1, F2), a field

power cube, two wiring harnesses,

bracket support and mounting

hardware. The user provides the

F1/F2 conductors to the drive motor.

No other equipment is required.
To install the Kit, follow these

procedures.

Step 1 - Mount Field Kit
a. Remove screws from 1TB.
b. Remove screws from the support

bracket.

c. Remove screw leads 32 and 132

from 2TB.

d. Remove the support bracket

from the unit.

e. Mount the Field Supply Kit onto

the unit.

f. Reinstall leads 32 and 132 onto

2TB.

g. Mount 1TB to the Field Supply

Kit.

Wire the Field Supply

DĆC field supply voltage and

maximum field amperes are listed in

Table 2Ć1.

Step 1 - Wire Field Supply Power

Cube
Wire from the field supply power

cube to terminals 51 and 52 on 1TB

as shown in Figure 3Ć7.

AĆC

AĆC

+

1 TB

51

52

F1 F2

2TB

To

F1, F2

on motor

Figure 3Ć7. Connecting Field

Supply.