Rockwell Automation FlexPak Plus DC Drive User Manual

Page 41

Advertising
background image

5:11

Check for speed reference 0 to

8 VDC between terminals 126

and 57 (common).

Is

reference

voltage

present?

Check power supply voltages:

+11.2 VDC between terminals

56 and 57 (common)

-11.2 VDC between terminals

71 and 57 (Common)

Are

power supply

voltages

present?

At this point, if an Instrument

Interface Kit, Voltage Tach FolĆ

lower Kit, or a Dancer Follower

Kit is being used, go to Drive

Using Reference Kit" TroubleĆ

shooting Flowchart, if not,

continue.

Check reference voltage beĆ

tween terminals 426 and 57

(Common).

Start

Done

A

Check DĆC Bus voltage 0

to 90, or 180 VDC between

terminals 47 and 45.

Is DĆC Bus

voltage

present?

Check armature voltage

at terminals A1 and A2.

Replace

regulator board

B

Is armature

voltage

present?

Fixed?

See Note #1

Loose/open wiring or bad

FM Contactor power conĆ

tact between 47 and 45 to

A1 and A2.

Yes

No

Yes

No

Yes

No

Done

Fixed?

See Note #1

Yes

No

Possible motor or

motor wiring probĆ

lems.

Done

Fixed?

See Note #1

Yes

No

Correct the

problem

Check for 18 VAC beĆ

tween PINS 281 and

57, and PINS 282 and

57 of the regulator

board.

Note #1: Contact local sales/service office.

Yes

No

Yes

No

Go to

next page

Go to

next page

DANGER

SOME OF THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE

EXTREME CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION

COULD RESULT IN SEVERE BODILYINJURYOR LOSS OF LIFE.

Figure 5Ć8. M" Contactor PicksĆUp But Motor Does Not Run.