Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014
Chapter 5
PowerFlex 700H and 700S Drives - Frame 13 Procedures
6.
Disconnect the fan power supply wires from the top and bottom of the
fuse holder. Note that the red wires (+DC) are connected to the left side
terminal and the black wires (-DC) are connected to the right side
terminals.
7.
Remove the M4 x 8 mm POZIDRIV screw that secures the fuse holder
assembly.
8.
Install the AC or DC fan inverter fuses and fuse holder in the reverse order
of removal.
6
Converter Section
Inverter Section
7
Insulator
Fuse holder
PZ2
3.0 N
•
m (26.5 lb
•
in)
Note: Converter section shown