PowerFlex 700H and 700S Drives - Frame 9 Procedures
Chapter 1
9.
Install the new fan inverter assembly in the reverse order of removal.
IMPORTANT
If you are servicing a 400V/480V Frame 9 drive, insert the jumper on connector
X3 as shown here.
Connect Jumper to Connector X3
X8
X2
IMPORTANT
Verify that dip switch S1 on the new fan iverter board is properly configured, as
shown below.
X6
X1
X4
X5
X7
S1
X2
X8
1
ON
2
3
4
S1
1
ON
2
3
4
S1-1
S1-2
S1-3
S1-4
Off
Off
On
Off
Switch
Setting
To Indicate the Following:
S1
Off
50 Hz Fan Motor Frequency
S2
Off
220 V AC Motor Voltage
S3
On
230 V AC Motor Voltage
S4
Off
Frame Size 9…14