D10 expert, Dual discrete outputs, Self-diagnostic error modes – Banner D10 Series User Manual

Page 12: Gate input, Specifications

Advertising
background image

D10 Expert

Dual Discrete Outputs

12

P/N 64154 rev. F

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Self-Diagnostic Error Modes

In the unlikely event that the setup parameters are lost or become corrupt, the display will
continuously scroll: “USEr PSF Error.” Reteach the sensor to recover. If the problem persists,
contact your Banner representative for further information.

Gate Input

The pink wire is configured as a gate input. When this wire is pulled low (i.e., to the sensor
ground; 0-0.5V dc), it inhibits the outputs from switching, while all other sensor functions
continue to be enabled. This feature is useful for controlling when the outputs are allowed to
change states. Gate input function response time is 1 millisecond.

Required Fiber-Optic Cable

Banner P-Series plastic fibers

Sensing Beam

Visible red, 680 nm, or
Visible green, 525 nm, depending on model

Supply Voltage and Current

12 to 24V dc (10% maximum ripple) at less than 65 mA, exclusive of load

Supply Protection Circuitry

Protected against reverse polarity and transient voltage

Output Configuration

2 NPN or 2 PNP, depending on model

Output Rating

150 mA maximum load

OFF-state leakage current: < 10 µA at 24V dc

ON-state saturation voltage: NPN < 1.5V at 150 mA load

PNP < 2.5V at 150 mA load

Output Protection Circuitry

Protected against false pulse on power-up and continuous short-circuit

Output Response Time

Programmable, 50 microseconds, 200 microseconds, 1 millisecond, 2.5 milliseconds
NOTE: < 1 second delay on power-up; outputs do not conduct during this time.

Adjustments

Push-button or remote programming of response time, OFF-delay, light/dark operate, and display

Indicators

Four-digit digital display plus LED indicators for active channel, push-button lockout, OFF-delay and light/dark
operate selection; 2 yellow output indicators

Construction

Black ABS/polycarbonate alloy (UL94 V-0 rated) housing, clear polycarbonate cover

Environmental Rating

NEMA 1, IEC IP50

Connections

PVC-jacketed 2 m or 9 m (6.5' or 30') 6-wire integral cable or integral 6-pin Pico-style quick-disconnect

Operating Conditions

Temperature: -20° to +55°C (-4° to +131°F)

Storage Temperature: -20° to +80°C (-4° to +175°F)

Max. Rel. Humidity: 90% @ 50°C (non-condensing)

Number of Devices,

Stacked

Ambient Temperature

Rating

Load

Specification

3

55°C

150 mA

7

50°C

50 mA

10

45°C

50 mA

Installation

35 mm DIN rail or included mounting bracket

Certifications

Specifications