D10 expert, Dual discrete outputs, Two-point static teach (threshold) – Banner D10 Series User Manual

Page 4: Static teach and manual adjust, Teach output o n condition, Teach output off condition

Advertising
background image

D10 Expert

Dual Discrete Outputs

4

P/N 64154 rev. F

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Push Button

Remote

0.04 sec. ≤ T ≤ 0.8 sec.

Result

Access

Static

TEACH

Mode

• Press and
hold Static (-)
button > 2

seconds.

• No action required;
sensor is automatically
ready for 1st TEACH condition.

• Display flashes “1st
• Arrow icon turns red

TEACH

Output

O

N

Condition

• Present Output
ON condition.
• Click Static

button.

• Present Output ON
condition.
• Single-pulse the
remote line.

• Display flashes “2nd

TEACH

Output

OFF

Condition

• Present Output
OFF condition.
• Click Static

button.

• Present Output OFF
condition.
• Single-pulse the
remote line.

TEACH conditions acceptable:

• Display flashes “pass,” followed
by a number (denoting contrast);
see Figure 3.
• Sensor returns to RUN mode with
new settings.
• Arrow icon turns green

TEACH conditions unacceptable:

• Display flashes “fail” and
returns to “1st
• Arrow icon remains red
• After 60 seconds, sensor returns
to RUN mode (Arrow icon
turns green) without changing
settings.

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

dynamic

static

dynamic

static

dynamic

static

dynamic

static

dynamic

static

Two-Point Static TEACH (Threshold)

• Establishes a single switching threshold

• Threshold position is adjustable using “+” and “-” buttons (see Manual Adjust, page 9)

Static TEACH is the traditional setup method, used when two conditions can be presented
by the user. The sensor locates a single sensing threshold (the switchpoint) midway between
the two taught conditions, with the Output ON condition on one side, and the Output OFF
condition on the other (see Figure 2).

The first condition taught is the ON condition. The Output ON and OFF conditions can be
reversed by changing Light/Dark Operate status in SETUP mode (see page 10).

Static TEACH and Manual Adjust

Using Manual Adjust with Static TEACH moves the switching threshold.

Sensor positions

threshold midway

between taught conditions

Sensor positions

threshold midway

between taught conditions

Darkest

(no signal)

Darkest

(no signal)

Most Light

(saturated

signal)

Most Light

(saturated

signal)

Single

sensing

condition

Sensing window size

adjusted by

Manual Adjust

Output OFF

Output OFF

Output OFF

Output ON

Output ON

Darkest Taught

Condition

Lightest Taught

Condition

Position

adjusted by

Manual Adjust

Darkest

(no signal)

Most Light

(saturated

signal)

Output OFF

Output ON

2nd Taught

Condition

1st Taught

Condition

Position

adjusted by

Manual Adjust

Figure 2. Static TEACH (Light Operate

shown)

Contrast Values

500+

Excellent: Very stable operation.

100-500

Good: Minor sensing variables will
not affect sensing reliability.

32-99

Low: Minor sensing variables may
affect sensing reliability.

0-31

Marginal: Consider an alternate
sensing scheme.

Figure 3. Contrast Values