Carrier AQUAZONE PSV User Manual

Page 13

Advertising
background image

13

Optional pressure-rated hose assemblies designed specifi-

cally for use with Carrier units are available. Similar hoses can

be obtained from alternate suppliers. Supply and return hoses

are fitted with swivel-joint fittings at one end to prevent kink-

ing during installation.

Refer to Fig. 14 for an illustration of a supply/return hose

kit. Male adapters secure hose assemblies to the unit and risers.

Install hose assemblies properly and check them regularly to

avoid system failure and reduced service life.

Step 8 — Wire Field Power Supply

All field-installed wiring, including the electrical ground,

MUST comply with the National Electrical Code (NEC) as

well as applicable local codes. In addition, all field wiring must

conform to the Class II temperature limitations described in the

NEC.

Refer to unit wiring diagrams Fig. 15-25 for a schematic of

the field connections, which must be made by the installing (or

electrical) contractor. Refer to Tables 4-6 for fuse sizes.

Consult the unit wiring diagram located on the inside of the

compressor access panel to ensure proper electrical hookup.

The installing (or electrical) contractor must make the field

connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as

shown in electrical data shown in Tables 4-6.

Make all final electrical connections with a length of flexi-

ble conduit to minimize vibration and sound transmission to

the building.
POWER CONNECTION — Make line voltage connection

by connecting the incoming line voltage wires to the line

side of the compressor contactor terminal as shown in

Fig. 26. See Tables 4-6 for amperage ratings to provide cor-

rect wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be

within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must

be balanced within 2%. Use the following formula to deter-

mine the percentage voltage imbalance:
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.

This amount of phase imbalance is satisfactory as it is

below the maximum allowable 2%.

Operation on improper line voltage or excessive phase

imbalance constitutes abuse and may cause damage to electri-

cal components.
NOTE: If more than 2% voltage imbalance is present, contact

your local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory

wired for 208 volts. The transformers may be switched to

230-volt operation by switching the red (208 volt) wire with

the orange (230 volt) wire at the L1 terminal.
460-VOLT

OPERATION

Units using 460-v and an

ECM (electronically commutated motor) fan motor, modulat-

ing HWR, and/or internal secondary pump will require a

neutral wire from the supply side in order to feed accessory

with 265-v.

CAUTION

Backup wrench is required when tightening water connec-

tions to prevent water line damage. Failure to use a backup

wrench could result in equipment damage.

WARNING

To avoid possible injury or death due to electrical shock,

open the power supply disconnect switch and secure it in

an open position during installation.

CAUTION

Use only copper conductors for field-installed electrical

wiring. Unit terminals are not designed to accept other

types of conductors. Failure to use copper conductors could

result in equipment damage.

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%

Rib Crimped

Length

(2 ft Length Standard)

Swivel
Brass
Fitting

Brass
Fitting

MPT

Fig. 14 — Supply/Return Hose Kit

A50-7734

Advertising
This manual is related to the following products: