Caution – Carrier AQUAZONE PSV User Manual

Page 4

Advertising
background image

4

Before installing any of the system components, be sure to

examine each pipe, fitting, and valve, and remove any dirt or

foreign material found in or on these components.

INSPECT UNIT — To prepare the unit for installation, com-

plete the procedures listed below:

1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the

correct unit has been shipped.

2. Do not remove the packaging until the unit is ready for

installation.

3. Verify that the unit’s refrigerant tubing is free of kinks or

dents, and that it does not touch other unit components.

4. Inspect all electrical connections. Be sure connections are

clean and tight at their terminations.

5. Loosen compressor bolts until the compressor rides freely

on springs. Remove shipping restraints.

6. Remove the four

1

/

4

in. shipping bolts from compressor

support plate (two bolts on each side) to maximize vibra-

tion and sound alternation.

7. Remove any blower support cardboard from inlet of the

blower.

8. Locate and verify any accessory kit located in compressor

and/or blower section.

9. Remove any access panel screws that may be difficult to

remove once unit is installed.

CAUTION

DO NOT store or install units in corrosive environments or

in locations subject to temperature or humidity extremes

(e.g., attics, garages, rooftops, etc.). Corrosive conditions

and high temperature or humidity can significantly reduce

performance, reliability, and service life. Always move

units in an upright position. Tilting units on their sides may

cause equipment damage.

CAUTION

Failure to remove shipping brackets from spring-mounted

compressors will cause excessive noise and could cause

component failure due to added vibration.

Field-Supplied
Electric Heat
(if applicable)

Filter Access

Integral hanger support-
pre-attached in factory

Field-supplied transition to
minimize pressure loss

3/8” threaded rods

(by others)

Return Air
(Ductwork
not shown)

Thermostat

Wiring

Power Wiring

Balancing Valve (field-
installed accessory)

Stainless steel
braid hose
with integral
“J” swivel

3/8” Threaded

Rod (by others)

Supply Air

Insulated supply duct with
at least one 90 degree elbow
to reduce air noise
(field-supplied)

Flexible
Connection

Vibration Isolator

(white-compressor end

and red-blower end)

Washer

(by others)

Double Hex Nuts

(by others)

Unit Power

Unit Power
Disconnect
(by others)

Unit Hanger
(factory-
supplied)

Low Pressure Drop Water
Control Valve (optional)

(field-installed accessory)

Ball Valve with optional
integral P/T plug (typical for supply
and return piping)


(field-installed accessory)

(field-installed
accessory)

Aux Electric
Heat Disconnect

Water In

Water Out

Building

Loop

Fig. 1 — Typical Installation — 50PSH Unit

UNIT HANGER ISOLATION DETAIL

A50-7728