HWR APPLICATION CONSIDERATIONS — Unlike

most hot gas reheat options, the HWR option will operate

over a wide range of entering-water temperatures (EWTs).

Special flow regulation (water regulating valve) is not

required for low EWT conditions. However, below 55 F,

supply-air temperatures cannot be maintained at 72 F

because the cooling capacity exceeds the reheat coil capac-

ity at low water temperatures. Below 55 F, essentially all

water is diverted to the reheat coil (no heat of rejection to

the building loop). Although the HWR option will work fine

with low EWTs, overcooling of the space may result with

well water systems or, on rare occasions, with ground loop

(geothermal) systems (NOTE: Extended range units are

required for well water and ground loop systems). Since

dehumidification is generally only required in cooling, most

ground loop systems will not experience overcooling of the

supply-air temperature. If overcooling of the space is a con-

cern (e.g., computer room well water application), auxiliary

heating may be required to maintain space temperature

when the unit is operating in the dehumidification mode.

Water source heat pumps with HWR should not be used as

makeup air units. These applications should use equipment

specifically designed for makeup air.

HWR COMPONENT FUNCTIONS — The proportional

controller operates on 24 VAC power supply and automatically

adjusts the water valve based on the supply-air sensor. The

supply-air sensor senses supply-air temperature at the blower

inlet, providing the input signal necessary for the proportional

control to drive the motorized valve during the reheat mode of

operation. The motorized valve is a proportional actuator/three-

way valve combination used to divert the condenser water

from the coax to the hydronic reheat coil during the reheat

mode of operation. The proportional controller sends a signal

to the motorized valve based on the supply-air temperature

reading from the supply air sensor.

The loop pump circulates condenser water through the hy-

dronic reheat coil during the reheat mode of operation (refer to

Fig. 34). In this application, the loop pump is only energized

during the reheat mode of operation. The hydronic coil is uti-

lized during the reheat mode of operation to reheat the air to the

set point of the proportional controller. Condenser water is di-

verted by the motorized valve and pumped through the hydron-

ic coil by the loop pump in proportion to the control set point.

The amount of reheating is dependent on the set point and how

far from the set point the supply air temperature is. The factory

set point is 70 to 75 F, generally considered "neutral" air.

Table 17 — HWR Operating Modes

*Not applicable for single stage units; Full load operation for dual

capacity units.

†Cooling input takes priority over dehumidify input.

**Deluxe D is programmed to ignore the H demand when the unit is

in heating mode.

NOTE: On/Off is either on or off.

MODE

INPUT

OUTPUT

O

G

Y1

Y2*

H

O

G

Y1

Y2*

Reheat

No Demand

On/Off

Off

Off

Off

Off

On/Off

Off

Off

Off

Off

Fan Only

On/Off

On

Off

Off

Off

On/Off

On

Off

Off

Off

Cooling Stage 1

On

On

On

Off

Off

On

On

On

Off

Off

Cooling Stage 2

On

On

On

On

Off

On

On

On

On

Off

Cooling and Dehumidistat

On

On

On

On/Off

On

On

On

On

On/Off

Off

Dehumidistat Only

On/Off

Off

Off

Off

On

On

On

On

On

On

Heating Stage 1

Off

On

On

Off

Off

Off

On

On

Off

Off

Heating Stage 2

Off

On

On

On

Off

Off

On

On

On

Off

Heating and Dehumidistat**

Off

On

On

On/Off

On

Off

On

On

On/Off

Off

Fig. 34 — HWR Schematic

Water Out
(To Water Loop)

Water In
(From Water Loop)

Mixing Valve

COAX

Evaporator Coil

Reheat

Coil

Refrigerant Out

(Cooling)

Refrigerant In

(Cooling)

Entering Air

Leaving

Air

Internal Pump

NOTE: All components shown are
internal to the heat pump unit.

a50-8145