Appendix a — wshp screen open configuration (cont) – Carrier AQUAZONE PSV User Manual

Page 63

Advertising
background image

63

APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

LEGEND

SCREEN NAME

POINT NAME

PASSWORD

LEVEL

EDITABLE

RANGE

DEFAULT

NOTES

Configuration

Alarm

Configuration

SPT Occupied Alarm

Hysteresis

Admin Password

level access only

X

2 - 20

F

5

F

Defines the hysteresis applied above

the cooling and below the heating set

points before an alarm condition will

occur

SPT Alarm Delay

X

0 - 30 min per degree

10 min

Used to calculate the delay time before

an alarm is generated after the alarm

condition occurs

SPT Unoccupied Low

Alarm Temperature

X

35 - 90 F

45 F

Defines the fixed unoccupied

ow SPT alarm limit

SPT Unoccupied High

Alarm Temperature

X

45 - 100 F

95 F

Defines the fixed unoccupied

high SPT alarm limit

SAT Low SAT

Alarm Limit

X

15 - 90 F

45 F

Defines the fixed minimum

SAT alarm limit

SAT High SAT

Alarm Limit

X

90 - 175 F

120 F

Defines the fixed maximum

SAT alarm limit

Condensate Overflow

Alarm Delay

X

5 - 600 sec

10 sec

Defines the delay time before an alarm

is generated after the alarm condition

occurs

Space Humidity Occupied

High Alarm Limit

X

45% - 100%

100%

Defines the fixed occupied

high space RH alarm limit

Space Humidity Alarm

Delay

X

0 - 30 min per % RH

5 min

Used to calculate the delay time before

an alarm is generated after the alarm

condition occurs

Space Humidity Unoccu-

pied High Alarm Limit

X

45% - 100%

100%

Defines the fixed unnoccupied

high space RH alarm limit

IAQ/Ventilation Occupied

High Alarm Limit

X

0 - 9999 ppm

1100 ppm

Defines the fixed occupied high

space IAQ/Ventilation alarm limit

IAQ/Ventilation

Alarm Delay

X

0.1 - 1.0 min per ppm

0.25 min

Used to calculate the delay time before

an alarm is generated after the alarm

condition occurs

Rnet Sensor SPT Alarm

X

Ignore/Display

Ignore

Determines if the SPT alarm is

displayed on the local Rnet sensor

Rnet Sensor SAT Alarm

X

Ignore/Display

Ignore

Determines if the SAT alarm is

displayed on the local Rnet sensor

Rnet Sensor Compressor

Lockout Alarm

X

Ignore/Display

Display

Determines if the Compressor Lockout

alarm is displayed on the local Rnet

sensor

Rnet Sensor Condenser

Water Temperature Alarm

X

Ignore/Display

Display

Determines if the Condenser Water

Temperature alarm is displayed on the

local Rnet sensor

Rnet Sensor Condensate

Overflow Alarm

X

Ignore/Display

Display

Determines if the Condensate

Overflow alarm is displayed on the

local Rnet sensor

Rnet Sensor Dirty

Filter Alarm

X

Ignore/Display

Display

Determines if the Dirty Filter alarm is

displayed on the local Rnet sensor

Rnet Sensor Space

High Humidity Alarm

X

Ignore/Display

Ignore

Determines if the High Space

RH alarm is displayed on the

local Rnet sensor

Configuration

Linkage

Loop Control Network

Number

See TPI

Loop Control Network

Address

See TPI

Number of Linked Heat

Pumps

See TPI

°

°

°

°

°

°

°

°

°

°

BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration