Table 6 — 50PSH, PSV, PSD Electrical Data, ECM Motor

LEGEND

NOTES:

1. The 460-v units using an ECM (electronically commutated motor) fan

motor, modulating HWR, and/or an internal secondary pump will require
a neutral wire from the supply side in order to feed the accessory with
265-v.

2. Unit sizes 006-012 are not available with ECM motors.

50PS

UNIT

SIZE

RATED

VOLTAGE

V-Ph-Hz

VOLTAGE

MIN/MAX

COMPRESSOR

FAN

MOTOR

FLA

TOTAL

UNIT

FLA

MIN

CIRCUIT

AMP

MAX

FUSE/

HACR

UNITS WITH ECM MOTOR AND HWR

RLA

LRA

Qty

REHEAT

PUMP

FLA

TOTAL

UNIT

FLA

MIN

CIRCUIT

AMP

MAX

FUSE /

HACR

018

208/230-1-60

197/254

9.0

48.0

1

4.3

13.3

15.6

20

0.8

14.1

16.4

25

265-1-60

239/292

8.4

40.0

1

4.1

12.5

14.6

20

0.7

13.2

15.3

20

024

208/230-1-60

197/254

12.8

60.0

1

4.3

17.1

20.3

30

0.8

17.9

21.1

30

208/230-3-60

197/254

8.0

55.0

1

4.3

12.3

14.3

20

0.8

13.1

15.1

20

460-3-60

414/506

4.0

22.4

1

4.1

8.1

9.1

15

0.7

8.8

9.8

15

030

208/230-1-60

197/254

13.5

61.0

1

4.3

17.8

21.2

30

0.8

18.6

22.0

35

265-1-60

239/292

10.9

58.0

1

4.1

15.0

17.7

25

0.7

15.7

18.4

25

208/230-3-60

197/254

8.3

63.0

1

4.3

12.6

14.7

20

0.8

13.4

15.5

20

460-3-60

414/506

4.5

27.0

1

4.1

8.6

9.7

15

0.7

9.3

10.4

15

036

208/230-1-60

197/254

14.7

72.5

1

4.3

19.0

22.7

35

0.8

19.8

23.5

35

265-1-60

239/292

12.5

61.0

1

4.1

16.6

19.7

30

0.7

17.3

20.4

30

208/230-3-60

197/254

10.4

63.0

1

4.3

14.7

17.3

25

0.8

15.5

18.1

25

460-3-60

414/506

4.5

32.0

1

4.1

8.6

9.7

15

0.7

9.3

10.4

15

042

208/230-1-60

197/254

15.4

83.0

1

4.3

19.7

23.6

35

0.8

20.5

24.4

35

208/230-3-60

197/254

11.5

77.0

1

4.3

15.8

18.7

30

0.8

16.6

19.5

30

460-3-60

414/506

5.1

35.0

1

4.1

9.2

10.5

15

0.7

9.9

11.2

15

048

208/230-1-60

197/254

20.5

109.0

1

7.0

27.5

32.6

50

1.07

28.6

33.7

50

208/230-3-60

197/254

14.6

91.0

1

7.0

21.6

25.3

35

1.07

22.7

26.3

40

460-3-60

414/506

7.1

46.0

1

6.9

14.0

15.8

20

1.07

15.1

16.8

20

060

208/230-1-60

197/254

26.9

145.0

1

7.0

33.9

40.6

60

1.07

35.0

41.7

60

208/230-3-60

197/254

17.6

123.0

1

7.0

24.6

29.0

45

1.07

25.7

30.1

45

460-3-60

414/506

9.6

64.0

1

6.9

16.5

18.9

25

1.07

17.6

20.0

25

070

208/230-1-60

197/254

30.1

158.0

1

7.0

37.1

44.6

70

1.07

38.2

45.7

70

208/230-3-60

197/254

20.5

155.0

1

7.0

27.5

32.6

50

1.07

28.6

33.7

50

460-3-60

414/506

9.6

75.0

1

6.9

16.5

18.9

25

1.07

17.6

20.0

25

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
HWR

Hot Water Reheat

LRA

Locked Rotor Amps

RLA

Rated Load Amps

COMPLETE C CONTROL

ECM CONTROL

BOARD

CAPACITOR

LINE

LOAD

COMPRESSOR CONTACTOR

TRANSFORMER

Fig. 26 — 50PSH,PSV,PSD Typical Single-Phase Line Voltage Power Connection

A50-7737