Carrier AQUAZONE PSV User Manual

Page 16

Advertising
background image

16

*Optional.

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BR

Blower Relay

CB

Circuit Breaker

CC

Compressor Contactor

CO

Condensate Overflow Sensor

COMPR — Compressor
DTS

Discharge Temp Switch

ECM

Electronically Commutated Motor

FP1

Water Coil Freeze Protection Sensor

FP2

Air Coil Freeze Protection Sensor

HP

High-Pressure Switch

HWG

Hot Water Generator

JW

Jumper Wire

LOC

Loss of Charge Pressure Switch

LWT

Leaving Water Temperature

MV

Motorized Valve

NEC

National Electric Code

P1

Field Wiring Terminal Block

LEGEND

RVS

Reversing Valve Solenoid

TRANS

Transformer

UPS

Unit Performance Sentinel

Factory Low Voltage Wiring
Factory Line Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Printed Circuit Trace
Optional Wiring

Relay/Contactor Coil

Thermistor

Condensate Pan

Circuit Breaker

Ground

Solenoid Coil

Relay Contacts - N.C.

Relay Contacts - N.O.

Capacitor

Temperature Switch

Low Pressure Switch

High Pressure Switch

Wire Nut

Splice Cap

LED

G

NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For

230 v operation, disconnect RED lead at L1 and attach ORANGE
lead to L1. Insulate open end of RED lead. Transformer is energy
limiting or may have circuit breaker.

4. FP1 thermistor provides freeze protection for water. When using

antifreeze solutions, cut JW3 jumper.

5. Check installation wiring information for specific thermostat hookup.

Refer to thermostat installation instructions for wiring to the unit.
Thermostat wiring must be “Class 1” and voltage rating equal to or
greater than unit supply voltage.

6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper

and dry contact will be available between AL1 and AL2.

7. Transformer secondary ground via Complete C board standoffs and

screws to control box. (Ground available from top two standoffs as
shown.)

8. Aquastat is supplied with unit and must be wired in series with the

hot leg to the pump. Aquastat is rated for voltage up to 277 v.

COMPLETE C CONTROLLER FAULT CODES

DESCRIPTION OF OPERATION

LED

ALARM RELAY

Normal Mode

ON

Open

Normal Mode with UPS Warning

ON

Cycle (Closed 5 Sec.

Open 25 Sec.)

Complete C is Non-Functional

OFF

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open

(Closed After 15 Min.)

Test Mode-No Fault in Memory

Flashing Code 1

Cycling Code 1

Test Mode-HP Fault in Memory

Flashing Code 2

Cycling Code 2

Test Mode-LP Fault in Memory

Flashing Code 3

Cycling Code 3

Test Mode-FP1 Fault in Memory

Flashing Code 4

Cycling Code 4

Test Mode-FP2 Fault in Memory

Flashing Code 5

Cycling Code 5

Test Mode-CO Fault in Memory

Flashing Code 6

Cycling Code 6

Test Mode-Over/Under Shutdown
in Memory

Flashing Code 7

Cycling Code 7

Test Mode-UPS in Memory

Flashing Code 8

Cycling Code 8

Swapped FP1/FP2 Lockout

Flashing Code 9

Cycling Code 9

Fig. 17 — Units with Complete C ECM Blower, Three-Phase (208/230 V)