Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

Capacitor

LED

G

NOTES:

1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208-240 60 Hz units are wired for 208v operation. Transformer is energy

limiting or may have circuit breaker.

4. FP1 thermistor provides low temperature protection for water. When

using antifreeze solutions, cut JW3 jumper.

5. Refer to multiple protocol controller (MPC), LON, or TSTAT Installation,

Application, and Operation Manual for control wiring to the wire from
PremierLink controller to “Y” Complete C when motorized valve is not
used. Thermostat wiring must be “Class 1” and voltage rating equal to or
greater than unit supply voltage.

6. 24v alarm signal shown. For dry contact, cut JW1 jumper and dry con-

tact will be available between AL1 and AL2.

7. Transformer secondary ground via green wire with yellow stripe from “C”

terminal to control box.

8. Aquastat is supplied with unit and must be wired in series with the hot

leg to the pump. Aquastat is rated for voltages up to 277v.

LEGEND

*Optional Wiring.

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BR

Blower Relay

CB

Circuit Breaker

CC

Compressor Contactor

CO

Sensor, Condensate Overflow

CR

Cooling Relay

DTS

Discharge Temp Switch

ECM

Electronically Commuted Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High Pressure Switch

HPWS

High Pressure Water Switch

HWG

Hot Water Generator

JW

Jumper Wire

LOC

Loss of Charge Pressure Switch

LWT

Leaving Water Temperature

MV

Motorized Valve

MVES

Motorized Valve End Switch

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

SAT

Saturated Air Temperature

TRANS

Transformer

UPS

Unit Performance Sentinel

Field Line Voltage Wiring

Field Low Voltage Wiring
Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

COMPLETE C CONTROLLER FAULT CODES

DESCRIPTION OF OPERATION

LED

ALARM RELAY

Normal Mode

ON

Open

Normal Mode with UPS Warning

ON

Cycle (Closed 5 Sec.

Open 25 Sec.)

Complete C is Non-Functional

OFF

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open (Closed After 15 Min.)

Test Mode-No Fault in Memory

Flashing Code 1

Cycling Code 1

Test Mode-HP Fault in Memory

Flashing Code 2

Cycling Code 2

Test Mode-LP Fault in Memory

Flashing Code 3

Cycling Code 3

Test Mode-FP1 Fault in Memory

Flashing Code 4

Cycling Code 4

Test Mode-FP2 Fault in Memory

Flashing Code 5

Cycling Code 5

Test Mode-CO Fault in Memory

Flashing Code 6

Cycling Code 6

Test Mode-Over/Under Shutdown
in Memory

Flashing Code 7

Cycling Code 7

Test Mode-UPS in Memory

Flashing Code 8

Cycling Code 8

Swapped FP1/FP2 Lockout

Flashing Code 9

Cycling Code 9

a50-8232

Fig. 20 — Units with Complete C and Premierlink™ Controller, Single-Phase (208/230 V)