Step 2 — check unit – Carrier AQUAZONE PSV User Manual

Page 3

Advertising
background image

3

Table 1 — Physical Data — 50PSH, PSV, PSD018-070 Units

LEGEND

*Unit sizes 006-012 not available on 50PSD unit.
NOTE: All units have spring compressor mountings, TXV expansion devices, and

1

/

2

-

in. and

3

/

4

-in. electrical knockouts.

Step 2 — Check Unit —

Upon receipt of shipment at

the jobsite, carefully check the shipment against the bill of

lading. Make sure all units have been received. Inspect the car-

ton or crating of each unit, and inspect each unit for damage.

Ensure the shipping company makes proper notation of any

shortages or damage on all copies of the freight bill. Concealed

damage not discovered during unloading must be reported to

the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all

necessary claims with the shipping company.

1. Be sure that the location chosen for unit installation pro-

vides ambient temperatures maintained above freezing.

Well water applications are especially susceptible to

freezing.

2. Be sure the installation location is isolated from sleeping

areas, private offices and other acoustically sensitive

spaces.
NOTE: A sound control accessory package may be used

to help eliminate sound in sensitive spaces.

3. Check local codes to be sure a secondary drain pan is not

required under the unit.

4. Be sure unit is mounted at a height sufficient to provide

an adequate slope of the condensate lines. If an appropri-

ate slope cannot be achieved, a field-supplied condensate

pump may be required.

5. Provide sufficient space for duct connection. Do not al-

low the weight of the ductwork to rest on the unit.

6. Provide adequate clearance for filter replacement and

drain pan cleaning. Do not allow piping, conduit, etc. to

block filter access.

7. Provide sufficient access to allow maintenance and

servicing of the fan and fan motor, compressor and coils.

Removal of the entire unit from the closet should not be

necessary.

8. Provide an unobstructed path to the unit within the closet

or mechanical room. Space should be sufficient to allow

removal of unit if necessary.

9. Provide ready access to water valves and fittings, and

screwdriver access to unit side panels, discharge collar,

and all electrical connections.

10. Where access to side panels is limited, pre-removal of the

control box side mounting screws may be necessary for

future servicing.

STORAGE — If the equipment is not needed immediately at

the jobsite, it should be left in its shipping carton and stored in a

clean, dry area of the building or in a warehouse. Units must be

stored in an upright position at all times. If carton stacking is

necessary, stack units a maximum of 3 high. Do not remove

any equipment from its shipping package until it is needed for

installation.
PROTECTION — Once the units are properly positioned on

the jobsite, cover them with either a shipping carton, vinyl film,

or an equivalent protective covering. Cap open ends of pipes

stored on the jobsite. This precaution is especially important in

areas where painting, plastering, or spraying of fireproof mate-

rial, etc. is not yet complete. Foreign material that accumulates

within the units can prevent proper start-up and necessitate

costly clean-up operations.

50PS UNIT SIZE

006*

009*

012*

018

024

030

036

042

048

060

070

COMPRESSOR (1 Each)

Rotary

Scroll

FACTORY CHARGE R-410A (oz)

24

32

34

50

56

58

70

80

80

136

144

ECM FAN MOTOR AND BLOWER

Fan Motor (Hp)

N/A

N/A

N/A

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

1

1

1

Blower Wheel Size (D x W) (in.)

N/A

N/A

N/A

9 x 7

9 x 7

9 x 7

11 x 10

11 x 10

11 x 10

11 x 10

11 x 10

PSC FAN MOTOR AND BLOWER
(3 Speeds)

Fan Motor (Hp)

1

/

25

1

/

20

1

/

8

1

/

6

1

/

5

1

/

3

1

/

2

1

/

2

3

/

4

1

1

High Static Fan Motor (Hp)

N/A

N/A

N/A

1

/

5

1

/

3

1

/

2

1

/

2

3

/

4

3

/

4

1

N/A

Blower Wheel Size (D x W) (in.)

6 x 5

6 x 5

6 x 5

9 x 7

9 x 7

9 x 7

10 x 10

10 x 10

10 x 10

11 x 10

11 x 10

Heat Exchanger Water Volume (gal.)

0.56

0.56

0.56

0.56

0.76

0.76

0.92

1.24

1.24

1.56

1.56

COAXIAL VOLUME (gal.)

.17

.29

.45

.56

.76

.76

.92

1.24

1.24

1.56

1.56

WATER CONNECTION SIZE, FPT (in.)

1

/

2

1

/

2

1

/

2

3

/

4

3

/

4

3

/

4

3

/

4

1

1

1

1

HWG CONNECTION SIZE, FPT (in.)

N/A

N/A

N/A

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

VERTICAL UPFLOW/DOWNFLOW

Air Coil Dimensions (H x W) (in.)

16 x 16

16 x 16

16 x 16

24 x 20

28 x 20

28 x 20

28 x 25

32 x 25

32 x 25

36 x 25

36 x 25

Throwaway Filter, Standard 1-in.,

Qty...Size

1...

16 x 20

1...

16 x 20

1...

16 x 20

1...

24 x 24

1...

28 x 24

1...

28 x 24

1...

28 x 30

2...

16 x 30

2...

16 x 30

1...

16 x 30;

1...

20 x 30

1...

16 x 30;

1..

20 x 30

Weight

Operating (lb)

126

146

150

252

266

268

327

414

416

441

443

Packaged (lb)

136

156

160

262

276

278

337

424

426

451

453

HORIZONTAL

Air Coil Dimensions (H x W) (in.)

16 x 16

16 x 16

16 x 16

18 x 27

18 x 31

18 x 31

20 x 35

20 x 40

20 x 40

20 x 45

20 x 45

Throwaway Filter, Standard 1-in.,

Qty...Size

1...

16 x 20

1...

16 x 20

1...

16 x 20

2...

18 x 18

2...

18 x 18

2...

18 x 18

1...

12 x 20;

1...

20 x 25

1...

18 x 20;

1...

20 x 24

1...

18 x 20;

1...

20 x 24

2...

20 x 24

2...

20 x 24

Weight

Operating (lb)

136

156

160

257

266

268

327

414

416

441

443

Packaged (lb)

146

166

170

267

276

278

337

424

426

451

453

Corner (lb)

Left Front

45.0

55.0

56.0

74.7

78.8

79.4

104.4

144.3

145.0

182.3

183.1

Left Rear

33.0

36.0

37.0

66.2

69.9

70.4

83.7

97.7

98.1

78.4

78.8

Right Front

30.0

33.0

34.0

63.6

67.2

67.7

74.9

92.1

92.6

72.5

72.8

Right Rear

28.0

32.0

33.0

47.5

50.2

50.5

64.0

79.9

80.3

107.8

108.3

ECM — Electronically Controlled Motor

PSC — Permanent Split Capacitor