Carrier AQUAZONE PSV User Manual

Page 51

Advertising
background image

51

The bulb must be secured to the pipe using a copper strap.

The use of heat transfer paste between the bulb and the pipe

will also help ensure optimum performance.

The bulb must also be properly insulated to eliminate any

influence on valve operation by the surrounding conditions.

Cork tape is the recommended insulation as it can be molded

tight to the bulb to prevent air infiltration.
Causes of TXV Failure — The most common causes of TXV

failure are:

1. A cracked, broken, or damaged sensing bulb or capillary

can be caused by excessive vibration of the capillary dur-

ing shipping or unit operation.
If the sensing bulb is damaged or if the capillary is

cracked or broken, the valve will be considered failed and

must be replaced. Replacement of the TXV “power head”

or sensing bulb, capillary, diaphragm assembly is possible

on some TXVs. The power head assembly screws onto

most valves, but not all are intended to be replaceable. If

the assembly is not replaceable, replace the entire valve.

2. Particulate debris within the system can be caused by sev-

eral sources including contaminated components, tubing,

and service tools, or improper techniques used during

brazing operations and component replacement.
Problems associated with particulate debris can be com-

pounded by refrigerant systems that use POE (polyol es-

ter oil). POE oil has solvent-like properties that will clean

the interior surfaces of tubing and components. Particu-

lates can be released from interior surfaces and may mi-

grate to the TXV strainer, which can lead to plugging of

the strainer.

3. Corrosive debris within the system may happen after a

failure, such as a compressor burn out, if system was not

properly cleaned.

4. Noncondensables may be present in the system. Non-

condensables includes any substance other than the

refrigerant or oil such as air, nitrogen, or water. Contami-

nation can be the result of improper service techniques,

use of contaminated components, and/or improper evacu-

ation of the system.

Symptoms — The symptoms of a failed TXV can be varied

and will include one or more of the following:
• Low refrigerant suction pressure
• High refrigerant superheat

• High refrigerant subcooling
• TXV and/or low pressure tubing frosting

• Equalizer line condensing and at a lower temperature than

the suction line or the equalizer line frosting

• FP1 faults in the heating mode in combination with any of

the symptoms listed above

• FP2 faults in the cooling mode in combination with any of

the symptoms listed above. Some symptoms can mimic a

failed TXV but may actually be caused be another problem.
Before conducting an analysis for a failed TXV the follow-

ing must be verified:
• Confirm that there is proper water flow and water tempera-

ture in the heating mode.

• Confirm that there is proper airflow and temperature in the

cooling mode.

• Ensure coaxial water coil is clean on the inside; this applies

to the heating mode and may require a scale check.

• Refrigerant may be undercharged. To verify, subcooling and

superheat calculations may be required.

Diagnostics—Several tests may be required to determine if

a TXV has failed. The following tools may be required for

testing:

1. Refrigerant gage manifold compatible with the refriger-

ant in the system

2. Digital thermometer, preferably insulated, with wire leads

that can be connected directly to the tubing

3. Refrigerant pressure-temperature chart for the refrigerant

used

To determine that a TXV has failed, verify the following:
• The suction pressure is low and the valve is non-responsive.

The TXV sensing bulb can be removed from the suction

line and warmed by holding the bulb in your hand. This

action should result in an increase in the suction pressure

while the compressor is operating. The sensing bulb can

also be chilled by immersion in ice water, which should

result in a decrease in the suction pressure while the

compressor is operating. No change in the suction pres-

sure would indicate a nonresponsive valve.

• Simultaneous LOW suction pressure, HIGH refrigerant

subcooling and HIGH superheat may indicate a failed

valve.

• LOW suction pressure, LOW subcooling and HIGH super-

heat may indicate an undercharge of refrigerant. HIGH sub-

cooling and LOW superheat may indicate an overcharge of

refrigerant. The suction pressure will usually be normal or

high if there is an overcharge of refrigerant.

• LOW suction pressure and frosting of the valve and/or

equalizer line may indicate a failed valve. However, these

symptoms may also indicate an undercharge of refrigerant.

Calculate the subcooling and superheat to verify a failed

valve or refrigerant charge issue.

Repair

WARNING

Puron

®

refrigerant (R-410A) operates at higher pressure

than R-22, which is found in other WSHPs. Tools such as

manifold gages must be rated to withstand the higher pres-

sures. Failure to use approved tools may result in a failure

of tools, which can lead to severe damage to the unit, injury

or death.

WARNING

Most TXVs are designed for a fixed superheat setting and

are therefore considered non-adjustable. Removal of the

bottom cap will not provide access for adjustment and can

lead to damage to the valve or equipment, unintended vent-

ing of refrigerant, personal injury, or possibly death.

CAUTION

Use caution when tightening the strap. The strap must be

tight enough to hold the bulb securely but caution must be

taken not to over-tighten the strap, which could dent, bend,

collapse or otherwise damage the bulb.

CAUTION

Puron refrigerant (R-410A) requires the use of synthetic

lubricant (POE oil). Do not use common tools on systems

that contain R-22 refrigerants or mineral oil. Contamina-

tion and failure of this equipment may result.

Advertising
This manual is related to the following products: