HEATING CYCLE ANALYSIS

COOLING CYCLE ANALYSIS

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (GPM) x

TEMP. DIFF. (DEG. F) x

FLUID FACTOR* =

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=

(DEG F)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=

(DEG F)

*Use 500 for water, 485 for antifreeze.

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

°F

°F

AIR

COIL

°F

PSI

FLUID OUT

FLUID IN

°F

PSI

LOOK UP PRESSURE DROP IN TABLE 31
TO DETERMINE FLOW RATE

°F

LIQUID LINE

PSI

°F

SAT

a50-8494

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

°F

°F

AIR

COIL

°F

PSI

FLUID OUT

FLUID IN

°F

PSI

LOOK UP PRESSURE DROP IN TABLE 31
TO DETERMINE FLOW RATE

°F

LIQUID LINE

PSI

°F

SAT

a50-8495

97B0038N04