APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)

LEGEND

SCREEN NAME

POINT NAME

PASSWORD

LEVEL

EDITABLE

RANGE

DEFAULT

NOTES

Configuration

Set Points

Occupied Heating

User/Admin

Password level

access

X

40 - 90 F

72 F

Defines the Occupied

Heating Set Point

Occupied Cooling

X

55 - 99 F

76 F

Defines the Occupied

Cooling Set Point

Unoccupied Heating

X

40 - 90 F

55 F

Defines the Unoccupied

Heating Set Point

Unoccupied Cooling

X

55 - 99 F

90 F

Defines the Unoccupied

Cooling Set Point

Effective Heating

Set Point

X

0 - 10

F

Takes into effect bias (maximum

allowable set point deviation)

Effective Cooling

Set Point

X

0 - 10

F

Takes into effect bias (maximum

allowable set point deviation)

Optimal Start

Uses historical data to calculate

ramp up time so as to be at set point

at occupied/unoccupied time

Occupied RH

Set Point

X

0 - 100%

65%

Defines the control set point used

during occupied periods (Viewable

only if Humidity Sensor = Installed/

Determines when to start

Dehumidification when occupied)

Unoccupied RH

Set Point

X

0 - 100%

90%

Defines the control set point used

during unoccupied periods

(Viewable only if Humidity Sensor =

Installed/Determines when to start

Dehumidification when unoccupied)

DCV CTRL Start

Set Point

X

0 - 9999 ppm

500 ppm

Defines the control set point used to

start increasing ventilation during

occupied periods (Viewable only if

Ventilation DMP Type = DCV)

DCV Max CTRL

Set Point

X

0 - 9999 ppm

1050 ppm

Defines the control set point

used to define where the ventilation

will reach its maximum limit during

occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used

to determine DCV ending control

point)

Configuration

Schedule

Weekly Schedule

Start Time

User/Admin

Password level

access

X

00:00 - 23:59

06:00

Defines the start time for an

occupied period

End Time

X

00:00 - 24:00

18:00

Defines the ending time of an

occupied period

Mon

X

No/Yes

Yes

Determines if this day is included

in this schedule

Tue

X

No/Yes

Yes

Determines if this day is included

in this schedule

Wed

X

No/Yes

Yes

Determines if this day is included

in this schedule

Thur

X

No/Yes

Yes

Determines if this day is included

in this schedule

Fri

X

No/Yes

Yes

Determines if this day is included

in this schedule

Sat

X

No/Yes

No

Determines if this day is included

in this schedule

Sun

X

No/Yes

No

Determines if this day is included

in this schedule

Configuration

Schedule

Exception

Schedules 1 - 12

Start Month

User/Admin

Password level

access

X

0 - 12

0

Defines the start month of this

hoilday schedule

Start Day

X

0 - 31

0

Defines the start day of this holiday

schedule

Start Time

X

00:00 - 23:59

0:00

Determines the start time for this

schedule

End Month

X

0 - 12

0

Defines the month to end this

hoilday schedule

End Day

X

0 - 31

0

Defines the day to end this holiday

schedule

End Time

X

00:00 - 24:00

0:00

Determines the time to end this

schedule

°

°

°

°

°

°

°

°

°

°

BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration