Carrier AQUAZONE PSV User Manual

Page 35

Advertising
background image

35

Deluxe D Control Accessory Relay Configura-
tions —

The following accessory relay settings are applica-

ble for Deluxe D control:
CYCLE WITH FAN — In this configuration, the accessory

relay 1 will be ON any time the Fan Enable relay is on.
CYCLE WITH COMPRESSOR — In this configuration, the

accessory relay 2 will be ON any time the Compressor relay

is on.
DIGITAL NIGHT SET BACK (NSB) — In this configura-

tion, the relay will be ON if the NSB input is connected to

ground C.
NOTE: If there are no relays configured for digital NSB, then

the NSB and override (OVR) inputs are automatically config-

ured for mechanical operation.
MECHANICAL NIGHT SET BACK — When NSB input is

connected to ground C, all thermostat inputs are ignored. A

thermostat set back heating call will then be connected to the

OVR input. If OVR input becomes active, then the Deluxe D

control will enter night low limit (NLL) staged heating mode.

The NLL staged heating mode will then provide heating dur-

ing the NSB period.
WATER VALVE (SLOW OPENING) — If relay is configured

for Water Valve (slow opening), the relay will start 60 seconds

prior to starting compressor relay.
OUTSIDE AIR DAMPER (OAD) — If relay is configured for

OAD, the relay will normally be ON any time the Fan Enable

relay is energized. The relay will not start for 30 minutes fol-

lowing a return to normal mode from NSB, when NSB is no

longer connected to ground C. After 30 minutes, the relay will

start if the Fan Enable is set to ON.

START-UP

Use the procedure outlined below to initiate proper unit

start-up.
NOTE: This equipment is designed for indoor installation only.

Operating Limits

ENVIRONMENT — This equipment is designed for indoor

installation ONLY. Extreme variations in temperature, humidi-

ty and corrosive water or air will adversely affect the unit per-

formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name-

plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — Units start and operate

in an ambient temperature of 45 F with entering-air tempera-

ture at 50 F, entering-water temperature at 60 F and with both

air and water at the flow rates used.
NOTE: These operating limits are not normal or continuous

operating conditions. Assume that such a start-up is for the

purpose of bringing the building space up to occupancy tem-

perature. See Table 18 for operating limits.

1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.
3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the

line power to all heat pump units.

5. Operate unit in the cooling cycle. Refer to Table 14 for

unit operating limits.

NOTE: Three factors determine the operating limits of a unit:

(1) entering air temperature, (2) water temperature and (3)

ambient temperature. Whenever any of these factors are at a

minimum or maximum level, the other two factors must be at a

normal level to ensure proper unit operation. See Table 18.

Table 18 — Operating Limits —

50PSH, PSV, PSD Units

LEGEND

NOTE: Value in heating column is dry bulb only. Any wet bulb reading is
acceptable.

Scroll Compressor Rotation —

It is important to be

certain compressor is rotating in the proper direction. To

determine whether or not compressor is rotating in the proper

direction:

1. Connect service gages to suction and discharge pressure

fittings.

2. Energize the compressor.

3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:

1. Turn off power to the unit. Install disconnect tag.

2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.

The suction and discharge pressure levels should now move

to their normal start-up levels.

When the compressor is rotating in the wrong direction, the

unit makes more noise and does not provide cooling.

After a few minutes of reverse operation, the scroll com-

pressor internal overload protection will open, thus activating

the unit lockout. This requires a manual reset. To reset, turn the

thermostat on and then off.
NOTE: There is a 5-minute time delay before the compressor

will start.

Unit Start-Up Cooling Mode

1. Adjust the unit thermostat to the warmest position.

Slowly reduce the thermostat position until the compres-

sor activates.

2. Check for cool air delivery at unit grille a few minutes

after the unit has begun to operate.

3. Verify that the compressor is on and that the water flow

rate is correct by measuring pressure drop through the

heat exchanger using P/T plugs. See Table 19. Check the

elevation and cleanliness of the condensate lines; any

dripping could be a sign of a blocked line. Be sure the

condensate trap includes a water seal.

CAUTION

To avoid equipment damage, DO NOT leave system filled

in a building without heat during the winter unless anti-

freeze is added to system water. Condenser coils never

fully drain by themselves and will freeze unless winterized

with antifreeze.

WARNING

When the disconnect switch is closed, high voltage is

present in some areas of the electrical panel. Exercise cau-

tion when working with the energized equipment. Failure

to heed this warning may result in personal injury.

AIR LIMITS

COOLING (F)

HEATING (F)

Min. Ambient Air

45

39

Rated Ambient Air

80.6

68

Max. Ambient Air

110

85

Min. Entering Air

50

40

Rated Entering Air db/wb

80/67

68

Max. Entering Air db/wb

110/83

80

WATER LIMITS

Min. Entering Water

30

20

Normal Entering Water

50-110

30-70

Max. Entering Water

120

90

db

Dry Bulb

wb — Wet Bulb

Advertising
This manual is related to the following products: