NOTES:

1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/3/60

units. Transformer is energy limiting or may have circuit
breaker.

4. FP1 thermistor provides freeze protection for water. When

using antifreeze solutions, cut JW3 jumper.

5. Typical thermostat wiring shown. Refer to thermostat installa-

tion instructions for wiring to the unit. Thermostat wiring must
be Class 1 and voltage rating equal to or greater than unit sup-
ply voltage.

6. Factory cut JW1 jumper. Dry contact will be available between

AL1 and AL2.

7. Transformer secondary ground via Deluxe D board standoffs

and screws to control box. (Ground available from top two
standoffs as shown.)

LEGEND

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BMC

Blower Motor Capacitor

BR

Blower Relay

CB

Circuit Breaker

CC

Compressor Contactor

CO

Sensor, Condensate Overflow

DTS

Discharge Temperature Switch

ECM

Electronically Commutated Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HPWS

High-Pressure Water Switch

HWG

Hot Water Generator

JW1

Clippable Field Selection Jumper

LOC

Loss of Charge Pressure Switch

LON

Local Operating Network

MV

Motorized Valve

NEC

National Electrical Code

*Optional Wiring.

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

TRANS — Transformer

Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

Thermistor

Ground

8. Aquastat is supplied with unit and must be wired in series with

the hot leg to the pump. Aquastat is rated for voltages up to
277-v.

9. Blower motor is factory wired for medium and high speeds. For

any other combination of speeds, at the motor attach the BLK
wire to the higher of the two desired speed taps and the BLU
wire to the lower of the two desired speed taps.

10. Optional LON wires. Only connect if LON connection is desired

at the wall sensor.

11. Blower motor is factory wired for high and low speeds. No other

combination is available.

12. The 460-v units using an ECM (electronically commutated

motor) fan motor, modulating HWR (hot water reheat), and/or
an internal secondary pump will require a neutral wire from the
supply side in order to feed the accessory with 265-v.

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

Deluxe D

HP

LOC

FP1

FP2

RVS

CO

SEE NOTE 4

a50-8364

Fig 19 — Units with ECM, Deluxe D and LON Controller (460 V)