See Section 9.6.3 Step 1 for wiring instructions. In this mode the temperature probe
must be a BALCO 1K type probe.

Modbus Network

When selecting Network as the Outdoor Temp Source, The Temperature probe is
connected to a Modbus Temperature transmitter as defined in Section 9.6.3, Step 2.

o

When selecting Network as the Head Temp Source, a Modbus Address

(Outdoor Temp Addr) and Modbus Point (Outdoor Temp Point) must be
entered to Define the Modbus Address and Point of the Modbus temperature
transmitter.


BST Remote Signal (Default = 4-20ma / 1-5V)
The BST Remote Signl item will only be displayed if Remote Setpoint Mode is selected. The
unit’s Setpoint can be remotely controlled by an Energy Management System (EMS)

The BST Remote Signl item selections are as follows:

4-20ma / 1-5V

When the BST Remote Signl item is set to 4-20ma / 1-5V, a 4 to 20 mA/1 to 5 Vdc
signal, sent by an EMS or BAS, is used to change the unit's setpoint. The 4 mA/1V
signal is equal to the value entered in “BST Setpt Lo Limit” while a 20 mA /5V signal is
equal to the value entered in “BST Setpt Hi Limit”.






0-20ma / 0-5V

When the BST Remote Signl item is set to 0 - 20 mA/0 - 5 Vdc, 0 mA is equal to the

value entered in “BST Setpt Lo Limit” while a 20 mA /5V signal is equal to value entered
in “BST Setpt Hi Limit”.











20ma

0ma

4ma

20ma

Remote Setpoint

4-20ma
drive
current

BST Setpt Lo

Limit

BST Setpt Hi Limit

Remote Setpoint

BST Setpt Lo

Limit

BST Setpt Hi Limit

0-20ma
drive
current