Section 4 - control panel display messages, 1 startup & status messages, 2 fault messages – AERCO C-More Controls Manual June 2010 User Manual
Page 55: Startup & status messages, Fault messages, C-more controller for benchmark, innovation & kc

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 55 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
SECTION 4 - CONTROL PANEL DISPLAY MESSAGES
4.1 STARTUP & STATUS MESSAGES.
Startup and status messages are displayed on the VFD display on the front panel of the C-More
Control Panel. This display is comprised of two lines with 16 characters per line. The startup
and status messages which may appear in the display are listed in Tables 4-1.
4.2 FAULT MESSAGES.
Fault messages which may appear in the VFD display are listed in Table 4-2.
Table 4-1: Startup and Status Messages
MESSAGE
DESCRIPTION
DISABLED
HH:MM pm MM/DD/YY
Displayed if ON/OFF switch is set to OFF. The display also
shows the time and date that the unit was disabled.
STANDBY
Displayed when ON/OFF switch is in the ON position, but
there is no demand for heat. The time and date are also
displayed.
DEMAND DELAY
XX sec
Displayed if Demand Delay is active.
PURGING
XX sec
Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.
IGNITION TRIAL
XX sec
Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds.
FLAME PROVEN
Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
of flame strength.
WARMUP
XX sec
Displayed for 2 minutes during the initial warm-up only.
WAIT
Prompts the operator to wait.