Section 4 - control panel display messages, 1 startup & status messages, 2 fault messages – AERCO C-More Controls Manual June 2010 User Manual

Page 55: Startup & status messages, Fault messages, C-more controller for benchmark, innovation & kc

Advertising
background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 55 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

SECTION 4 - CONTROL PANEL DISPLAY MESSAGES

4.1 STARTUP & STATUS MESSAGES.

Startup and status messages are displayed on the VFD display on the front panel of the C-More
Control Panel. This display is comprised of two lines with 16 characters per line. The startup
and status messages which may appear in the display are listed in Tables 4-1.

4.2 FAULT MESSAGES.

Fault messages which may appear in the VFD display are listed in Table 4-2.

Table 4-1: Startup and Status Messages

MESSAGE

DESCRIPTION

DISABLED

HH:MM pm MM/DD/YY

Displayed if ON/OFF switch is set to OFF. The display also
shows the time and date that the unit was disabled.

STANDBY

Displayed when ON/OFF switch is in the ON position, but
there is no demand for heat. The time and date are also
displayed.

DEMAND DELAY

XX sec

Displayed if Demand Delay is active.

PURGING

XX sec

Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.

IGNITION TRIAL

XX sec

Displayed during ignition trial of startup sequence. The
duration of cycle counts up in seconds.

FLAME PROVEN

Displayed after flame has been detected for a period of 2
seconds. Initially, the flame strength is shown in %. After 5
seconds has elapsed, the time and date are shown in place
of flame strength.

WARMUP

XX sec

Displayed for 2 minutes during the initial warm-up only.

WAIT

Prompts the operator to wait.














Advertising
This manual is related to the following products: