3.2 FACTORY DEFAULTS

The factory default values for each menu item are summarized in Table 3-2.

Table 3-2: Default Settings

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler LN

Unit Size

2.0 MBTU

Fuel Type

Natural Gas

Boiler Mode
(If Unit Type = Boiler)

Constant Setpoint

Heater Mode
(If Unit Type = Water Heater)

Constant Setpoint

Remote Signal
(If Mode = Remote Setpoint, Direct Drive or

Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio
(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp
(If Outdoor Sensor = Enabled)

60°F

Temp Hi Limit

210°F

Max Valve Position

100%

Pump Delay Timer (If Unit Type = Boiler)

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

Low Fire Timer

2 sec