C-More Controller for Benchmark, Innovation & KC
USER MANUAL
Page 158 of 162
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
04/22/14
GF-112
Phone: 800-526-0288
OMM-0032_0E
7.
S2 – R1 Switch (See Detail B of Figure D1): Set R1 switch to ON (UP) position if an O2
(Oxygen) sensor is NOT installed. Set R1 switch to the OFF (down) position in O2 sensor IS
installed.
8.
After the DIP switches have been set, reposition the Front Panel Assembly on the chassis
and secure it in place with the four screws.
9.
This completes the procedure for setting the DIP switches. Return the unit to service use.