C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 49 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 3-2: Default Settings - Continued

MENU & OPTION

FACTORY DEFAULT

Configuration Menu (Continued)

Setpt Limiting

Disabled

Setpt Limit Band

5°F

Network Timeout

30 Seconds

HI DB Setpt En

30

Demand Offset

10

Deadband High

2

Deadband Low

2

Spark Monitor

Disabled

Spark Current

Tuning Menu

Prop Band

70°F (Boiler), 8°F (Water Heater)

Integral Gain

1.00 (Boiler), 1.60 (Water Heater)

Derivative Time

0.00 min (Boiler), 0.10 min (Water Heater)

Min Load Adj (If Unit Type = Water Heater)

0°F

Max Load Adj (If Unit Type = Water Heater)

0°F

FFWD Temp Adj (If Unit Type = Water
Heater)

N/A

Outlet Feedback (If Unit Type = Water
Heater)

On

Feedback Gain (If Unit Type = Water Heater)

0.05

Breakpoint At 20% (If Unit Type = Water
Heater)

114°F

Breakpoint At 10% (If Unit Type = Water
Heater)

130°F

Breakpoint At 0% (If Unit Type = Water
Heater)

135°F

Warmup Prop Band

Default = 95

Warmup Int Gain

Default = 50

Warmup PID Timer

Default = 20

Reset Defaults?

No