Table 3-2: Default Settings - Continued
MENU & OPTION
FACTORY DEFAULT
Configuration Menu (Continued)
Setpt Limiting
Disabled
Setpt Limit Band
5°F
Network Timeout
30 Seconds
HI DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2
Spark Monitor
Disabled
Spark Current
Tuning Menu
Prop Band
70°F (Boiler), 8°F (Water Heater)
Integral Gain
1.00 (Boiler), 1.60 (Water Heater)
Derivative Time
0.00 min (Boiler), 0.10 min (Water Heater)
Min Load Adj (If Unit Type = Water Heater)
0°F
Max Load Adj (If Unit Type = Water Heater)
0°F
FFWD Temp Adj (If Unit Type = Water
Heater)
N/A
Outlet Feedback (If Unit Type = Water
Heater)
On
Feedback Gain (If Unit Type = Water Heater)
0.05
Breakpoint At 20% (If Unit Type = Water
Heater)
114°F
Breakpoint At 10% (If Unit Type = Water
Heater)
130°F
Breakpoint At 0% (If Unit Type = Water
Heater)
135°F
Warmup Prop Band
Default = 95
Warmup Int Gain
Default = 50
Warmup PID Timer
Default = 20
Reset Defaults?
No