3 analog in adjustment, 4 flow in adjustment, 5 supply gas pressure in adjustment – AERCO C-More Controls Manual June 2010 User Manual

Page 78: 6 gas plate dp in adjustment, 7 ma out adjustment, Analog in adjustment, Flow in adjustment, Supply gas pressure in adjustment, Gas plate dp in adjustment, Ma out adjustment

Advertising
background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 78 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

1.

Press the ▲ or ▼ arrow key until PWM In Adj is displayed along with the currently
entered adjustment percentage.

2. If the desired percentage is not displayed, press the CHANGE key. PWM In Adj will

begin to flash.

3.

Press the ▲ or ▼ arrow key to increment or decrement the display until the desired
adjustment percentage is displayed.

4. Press ENTER to store the selection.

5. Press BACK to exit the adjustment procedure.

6.2.3

Analog In Adjustment

The Analog Input Adjustment may be utilized when an external signal is used to change the
setpoint (Remote Setpoint Mode – boiler or heater), or drive the air/fuel valve position (Direct
Drive Mode – boiler only). This adjustment allows the 0 to 20 mA or 1 to 5 Vdc input to be
changed ±5.0% in 0.1 % increments. The default setting is 0.0%. To view or change this
adjustment, proceed as follows:

1. Press the

▲ or ▼ arrow key until Analog In Adj is displayed along with the current

adjustment percentage.

2. If the desired percentage is not displayed, press the CHANGE key. Analog In Adj will

begin to flash.

3. Press the

▲ or ▼ arrow key to increment or decrement the display until the desired

adjustment percentage is displayed.

4. Press ENTER to store the selection.

5. Press BACK to exit the adjustment procedure.

6.2.4

Flow In Adjustment.

The Flow Input Adjustment is not currently implemented in the C-More Control Panel. When
implemented, it will allow the water flow rate measured by a flow sensor to be adjusted ± 5%.

6.2.5

Supply Gas Pressure In Adjustment.

The Supply Gas Pressure Input Adjustment is not currently implemented in the C-More Control
Panel. When implemented, it will allow input flow rate to be adjusted ±5%.

6.2.6

Gas Plate dp In Adjustment

The Gas Plate dp Input Adjustment is not currently implemented in the C-More Control Panel.
When implemented, it will allow the input oxygen level to be adjusted ±5%.

6.2.7

mA Out Adjustment

The Milliamp (mA) Output Adjustment permits the output current to be adjusted from -1.0 mA to
+1.0 mA in 0.1 mA increments. The default setting is 0.0 mA. This function is associated with
the mA OUT terminals in the I/O Box. These terminals provide an output that can be used to
monitor setpoint, outlet temperature or valve position. The function to be monitored is selected
in the Configuration Menu. To view or adjust this setting, proceed as follows:

1. Press the

▲ or ▼ arrow key until mA Out Adj is displayed along with the current

adjustment setting in mA.

2. If the desired setting is not displayed, press the CHANGE key. mA Out Adj will begin

to flash.