2 operation time log, 3 sensor log, Operation time log – AERCO C-More Controls Manual June 2010 User Manual

Page 89: Sensor log, C-more controller for benchmark, innovation & kc

Advertising
background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 89 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 7-1: Sample Fault Log Display

No.

Fault Message

Cycle Date

Time

0

Direct Drive Signal Fault

609 1/10/02

8:42am

1

Low Gas Pressure

366 7/04/01

5:29pm

2

Loss of Power

0 1/01/01

11:50am

7.5.2

Operation Time Log

The Operation Time Log consists of a string of ASCII records stored in non-volatile memory
within the C-More Control Panel. Events such as power-up, ignition and turn-off are time
stamped. Data logged while the unit is running are run-length encoded. Data is logged or the
run-length incremented every 30 seconds. For a new run record to be logged, the fire rate or
flame strength must change by more than 5%, or the run mode must change. At steady-state,
the run-length is allowed to reach a maximum of 30 minutes before the record is logged. This
means that no more than 30 minutes of data can be lost if the unit loses power. Table 7-2
shows a sample Operation Time Log for a boiler: The Operation Time Log can only be
accessed through the RS232 interface using a laptop or other terminal device. Ten operation
time records are displayed for each T command entry. The operation time log can be cleared
ONLY by factory authorized personnel using the Clear Log option in the Factory menu.

NOTE

The Sensor (S) Log can store up to 1200 records. Therefore, to
view the most recently logged record, enter “S” followed by 0
(zero) and then press Enter (i.e. S0 <Enter>). To view earlier
records in reverse chronological order, enter S and press Enter.
To go back 200 or 700 records, enter S200 or S700, etc. and
press Enter.

Table 7-2: Sample Operation Time Log Display

Status

Valve

Position

Flame

Run Length

Date

Time

Off, Direct Drive

0

0

8

1/15/02

2:35pm

Run, Direct Drive

38

100

34

1/15/02

2:27pm

Run, Direct Drive

31

100

30

1/15/02

1:53am

Run, Direct Drive

35

100

2

1/15/02

1:23pm

Run, Direct Drive

29

100

0

1/15/02

1:21pm

Ignition

0

0

0

1/15/02

1:20pm

Off, Switch

0

0

35

1/15/02

12:30pm

Run, Manual

40

100

0

1/15/02

11:55am

Ignition

0

0

0

1/15/02

11:55am

Power-up

0

0

0

1/15/02

11:50am

7.5.3

Sensor Log

The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval
in the Diagnostics Menu. The log interval can vary from once every minute to once every day.
Table 7-3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint
mode.

Advertising
This manual is related to the following products: