Write Control
Values to BST

The BAS must write a 1 to this location for the first 4 values to
be copied across the SSD device, to the BST side. In normal
operation update the 4 registers 40200 through 40203 fairly
regularly. Once all four have been written, write a one to
40051. This is done to insure that all control values are copied
to the BST side of the SSD as a block.

40050

Write Op Values
to BAS

BST Master writes to this address to copy operational
parameters to the BAS side of the SSD. The BAS should
never read or write this address.

Reading Operational Data


The registers used to read operational data are 30100 through 30108 and 40054.

BAS
Register

Use

Description

30100

BST

This will typically always read as 2.

30101

BST setpoint

This is the temperature to which each boiler in the system will
control outlet temp. This values is not used in BST Mode.

30102

BST setback
setpoint

This is the temperature to which each boiler in the system will
control outlet temp to during the night setback period (if night
setback is enabled).

30103

BST setback start The time the setback period starts. This is expressed in

minutes since midnight. So for example 360 would correspond
to 6am.

30104

BST setback end The time the setback period ends. This is expressed in

minutes since midnight. If setback start and setback end are
the same value, there is no setback period.

30105

Auto Master

Zero “0” if the master unit is fixed, one “1” if it can
automatically failover to another unit after a fault.

30106

Average Outlet
Temperature

This is an average outlet temperature of all ignited boilers in
the system. Note! This item is for Water Heater units only.

30107

Units Enabled

This is the number of boilers in the system that can be lit off.

30108

Units Faulted

This is the number of boilers in the system that are faulted.

30109

Master Address

The Master Address is the comm address of the Master unit.

30110

BST Header
Temp

The BST Header Temp is the BST Header Temperature
reading.

30111

BST Outdoor
Temp

The BST Outdoor Temp is the Outdoor Temperature reading if
an outdoor temperature sensor is installed).

30112

BST Fire Rate

The BST Fire Rate is the Fire Rate command sent to all
ignited boilers.

30113

Units Ignited

This is the number of ignited units.

30114

BST Active
Setpoint

The actual setpoint the BST Master is working towards,
depending on the BST Setpoint Mode.

30115

BST Next On VP

The Fire Rate (Valve Position) above which the BST master
will light off another boiler if available.