Table 3-1: Menu Item Descriptions - Continued

MENU LEVEL & OPTION

DESCRIPTION

Calibration Menu

Stepper Fbk
(Not adjustable via
RS232 serial
communication)

Allows the Air/Fuel Valve stepper motor feedback current to be
calibrated at the 0% (fully closed) and 100% (fully open) positions.
Verification can also be accomplished at the 50% position.

PWM In Adj

Allows the Pulse Width Modulation (PWM) duty cycle to be adjusted
from -5.0% to +5.0% in 0.1% increments. Default = 0.0%.

Analog In Adj

Allows adjustment of the analog input from -5.0% to +5.0%. Default
= 0.0%.

Flow In Adj

Allows adjustment of the water Flow Rate Input from
-5.0% to +5.0%. Default = 0.0%.

Supply Gas Pressure In
Adj

Allows adjustment of the Supply Gas Pressure level from
-5.0% to +5.0% in 0.1 % increments. Default = 0.0%.

Gas Plate dp In Adj

Allows adjustment of the Gas Plate dp level from -5.0% to +5.0% in
0.1% increments. Default = 0.0%

mA Out Adj

Allows adjustment of the milliamp output from -5.0 mA to +5.0 mA.
Default = 0.0 mA

A/F Sensitivity

Allows adjustment of the Air/Fuel (A/F) Valve stepper motor
sensitivity to be adjusted from 1% to 5% in 1% increments. Default
is 2%.

Power Reset

Allows the Power Reset Option to be set to Auto or Manual. Default
is Auto.

Water Temp Reset

Allows the Water Temperature Reset function to be set to Auto or
Manual. Default is Auto.

Gas Press Reset

Allows the Gas Pressure Reset function to be set to Auto or
Manual. Default is Manual.

Min Off Time

Allows the minimum Off time to be set from 0 to 10 minutes. Default
= 1 min. (Boiler), 0 min. (Water Heater).

Heatr Tuning Dsp
(Water Heater Only)

Allows Heater Tuning Display to be Enabled or Disabled. Default is
Disabled.

Heatr Bkpt Dsp

Allows Heater Breakpoint Display to be Enabled or Disabled. When
Enabled, Breakpoints can be viewed and/or changed. Default is
Disabled. For water Heaters only.

Stop Level

Allows the Stop Level to be set to a valve position ranging from 0%
to the presently set Start Level. Default is 16%.

Start Level

Allows the Start Level to be set to a valve position ranging from the
presently set Stop Level to a maximum of 40%. Default is 20%.