6 sensor log int, Sensor log int, C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual

Page 83

Advertising
background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 83 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

6.3.6

Sensor Log Int

The Sensor Log Interval function permits the user to set the interval at which sensor readings
are recorded and stored in memory. By default, this option is set to OFF. However, if desired,
the Sensor Log Interval can be enabled and set to values ranging from 1 minute to 24 hours.

1.

Press the ▲ or ▼ arrow key until Sensor Log Int Off is displayed.

2. Press the CHANGE key. Sensor Log Int will begin to flash.

3.

Press the ▲ arrow key until the desired interval is displayed. The available choices
are:

(a)

1 Min

(b)

5 Min

(c)

15 Min

(d)

30 Min

(e)

1 hr

(f)

6 hrs

(g)

12 hrs

(h)

24 hrs

4. With the desired interval displayed, press ENTER to store the selection in memory.

5. Press BACK to exit the Sensor Log Int function.