Deadband High & Deadband Low

The Setpoint, Deadband High and Deadband Low define a PID Correction Deadband in which
the outlet temperature is allowed to drift. Allowing the outlet temperature to drift within this range
(Figure 3-1) minimizes Air/Fuel Valve corrections when deemed unnecessary.

When the Setpoint Temperature is reached, and remains stable for a period of 15 seconds, the
deadband mode is enabled and the °F or °C LED will flash on and off.

No Air Fuel Valve corrections will be attempted until the Outlet Temperature exits the Deadband
zone.


Setpoint

Setpoint + Deadband High

Setpoint - Deadband Low

Deadband

Zone

Outlet

Temp

Figure 3-1: PID Correction Deadband

The PID correction Deadband feature is active for both Boilers and Water Heaters. However,
this feature is not active in the Direct Drive Mode

3.1.2

HI DB Setpt EN Function

When firing at close to the shutdown limit (minimum Valve Position), the C-More will strive to
delay the unit shutdown to Standby Mode for as long as possible while still maintaining
adequate temperature control.

When the Valve Position is less than the Hi_DB_Setpt_En setting, (Figure 3-2), the Outlet
Temperature target is not Setpoint but Setpoint + Deadband_High.

This means that when operating close to the Shutdown Limit we will strive to increase the Valve
Position by changing the Setpoint Temperature to the Setpoint + Deadband_High Temperature
limit thus delaying the Shutdown.