C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 131 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Option 5 – Continued

On MASTER only:

3. Go to the BST Setpoint item and enter the Failsafe Setpoint.

4. Go to the BST Setup Menu item and set to Enabled.

5. Go to the BST Setpoint Mode item and select Remote Setpoint.

6. Go to the Head Temp Source item and select FFWD Temp.

7. Go to the BST Remote Signal and select either 4-20ma or 0-20ma.

When ALL C-More units have been configured:

7. Go to the BST Menu of the desired Master unit and set the BST Mode item to BST

MASTER.