Bas setup, Modbus points list, C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual

Page 140: Writing control values

Advertising
background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 140 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

3) To change from Degrees F, degrees C, to “counts”, select the appropriate value for the

SSD Format parameter. In most cases degrees F/C are used. The Counts option should
only be used for legacy installations.

BAS Setup

To setup BAS communications, use the following Modbus point tables below.

Reading Operational Data from a BST System and Writing Control Values

This document assumes that the BAS side of the SSD will be using Modbus, but equivalent
addressing and timing considerations apply to other communications methods (e.g. BACNET,
Modbus over TCP, etc.).

During normal operation, the BAS writes to two (2) address ranges on the SSD to send control
values to the BST system. It reads from two address ranges to retrieve operational state
information from the BST system.

Data is structured into header data (the BST system data) and then sections of data that is
repeated for each unit.

Modbus Points List

Writing Control Values


The registers used to write control values are 40200 through 40203 and 40051.

BAS
Register

Use

Description/Notes

40200

BST setpoint

This is the temperature each water heater in system will
control outlet temp to.

If the value written to BST setpoint is below the minimum
allowed value or above the Maximum allowed value, all
registers between 40200 and 40203 will be ignored on the
assumption that none of the data is valid.

40201

BST setback
setpoint

This is the temperature each water heater in system will
control outlet temp to during the night setback period (if night
setback is enabled).

40202

BST setback start The time the setback period starts. This is expressed in

minutes since midnight. For example 360 would correspond to
6am.

40203

BST setback end The time the setback period ends. This is expressed in

minutes since midnight. If setback start and setback end are
the same value, there is no setback period.

Advertising
This manual is related to the following products: