Benchmark 6000 DF Installation, Operation & Maintenance Manual
APPENDIX A – BOILER MENU DESCRIPTIONS
Page 156 of 219
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0096_0B
03/21/2014
Ph.: 800-526-0288
GF-141
APPENDIX A: BOILER MENU ITEM DESCRIPTIONS – Continued
MENU LEVEL & OPTION
DESCRIPTION
SETUP MENU
Password
Allows password to be entered.
Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.
Language
Permits selection of English, Spanish or French for
displayed messages. Default is English.
Time
Displays time from 12:00 am to 11:59 pm.
Date
Displays dates from 01/01/00 to 12/31/99
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.
Comm Address
For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.
Baud Rate
Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.
Min Upload Timer
Mandatory for AERCO OnAER Remote Data
Collection (ORDC). This parameter enables ORDC
and defines the minimum amount of time between
heartbeat data uploads in seconds. The COMM LED
will light during the upload.
Unit Alpha
Displays the first alphabetical character of the boiler
serial number [G (for “Gas-Fired”)]
Unit Year
Displays the year in which the boiler was
manufactured (00 – 99)
Unit Serial #
Displays the boiler numerical serial number (0000 –
9999). See the “Sample” serial # format below for a
boiler manufactured in 2013:
N-13-1234
Software Version
Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9).
Internal Setpoint
Allows internal setpoint to be set. Default is 130°F.
Unit Type
Allows selection of KC Boiler, KC Boiler LN, BMK
Boiler Std, BMK Blr Std Dual, BMK Boiler LN, BMK
Blr LN Dual, KC Water Heater, KC Wtr Heater LN,
Innovation WH